140DAI74000
Description
140DAI74000
Modicon Quantum Discrete Input Module
16 Channels, 230 V AC, 47–63 Hz, Standard Non‑Coating, No Fuse / No Diagnostic
English Specification Manual (Full Text, No Images)
1. General Description
Manufacturer: Schneider Electric
Series: Modicon Quantum (140 Series)
Module Type: AC Discrete Input Module, Standard, Non‑Fused, Non‑Diagnostic
Channels: 16 points (1 input word)
Form Factor: 1 slot, hot‑swappable
Coating: Standard non‑conformal coating
Weight: ~0.35 kg
Key Feature: Basic 230 V AC input, no fuse, no diagnostic LED
Application: General factory, machinery, assembly lines, standard 230 V AC signals without fuse/ diagnostic requirements
2. Electrical Specifications
Nominal Input Voltage: 230 V AC
Operating Frequency: 47 … 63 Hz
Logic 1 (ON):
165 … 264 V AC @ 57–63 Hz
175 … 264 V AC @ 47–53 Hz
Logic 0 (OFF): 0 … 40 V AC
Input Current:
11.5 mA max @ 57–63 Hz
9.7 mA max @ 47–53 Hz
Input Impedance:
26.5 kΩ (capacitive) @ 57–63 Hz
31.8 kΩ (capacitive) @ 47–53 Hz
Leakage Current: max 2.6 mA
Response Time:
OFF → ON: 0.75 … 4.9 ms
ON → OFF: 7.3 … 12.3 ms
Isolation (Channel‑to‑Bus): 1780 Vrms, 1 minute
Backplane Current: 180 mA
Power Dissipation: ~5.5 W max
Internal Power: Powered by Quantum backplane
Absolute Maximum Input:
200 V AC (1 cycle)
264 V AC (continuous)
300 V AC (10 s)
Fuse: None (no replaceable fuse on module)
Diagnostic: None (no F‑LED, no fault indication)
3. I/O & LED Indicators (Front)
IN0 … IN15 (Green LEDs) – Individual input status (ON = lit)
ACTIVE (Green LED) – Bus communication OK
No F‑LED – No fuse / diagnostic indication
4. Environmental Specifications
Operating Temperature: 0 °C … +60 °C
Storage Temperature: −40 °C … +85 °C
Relative Humidity: 5% … 95% non‑condensing
Altitude: ≤ 2,000 m (standard); up to 5,000 m derated
ESD: 4 kV contact / 8 kV air
EMI: 10 V/m (80–2000 MHz)
Protection Class: IP20
5. Physical & Mechanical
Dimensions (W × H × D): 35 × 122 × 52 mm (1 slot)
Mounting: Any single slot, hot‑swap compatible
Wiring: Screw terminals (field side)
Grouping: 1 group × 16 channels, 1 common
Field Wire Size: 0.5 … 2.5 mm²
6. Wiring & Connection
Common: One common for all 16 channels
Input: Apply 230 V AC between common and input terminal
Fuse: None – external fuse protection recommended
Shielding: Recommended for long cables; ground at one end only
7. Software Configuration
Unity Pro (recommended)
Concept v2.2+
ProWORX 32
Add 140DAI74000 (1 slot) to I/O map
Default input address: %I0 … %I15 (1 word)
Set input filter (software, optional)
Download to CPU
8. Troubleshooting
All IN LEDs OFF: Check 230 V AC supply and common wiring
ACTIVE OFF: Module not recognized; reseat or check backplane
Erratic Inputs: Poor grounding, noise, or loose terminals
No Fuse/DIAG: Use external circuit protection and monitoring
9. Certifications
CE (EN 55011, EN 61131‑2)
UL 508 / CSA C22.2 No. 142
CUL, FM Class I Div 2
RoHS compliant
10. Ordering Information
140DAI74000: Standard non‑coated, Non‑Fuse / Non‑Diagnostic (general environment)
140DAI74000C: Conformal coated, Non‑Fuse / Non‑Diagnostic (harsh environment)
Get a Quote