140DAI35300
Description
140DAI35300
Modicon Quantum Discrete Input Module
32 Channels, 24 V AC, 47–63 Hz, Standard Coating
English Specification Manual (Full Text, No Images)
1. General Description
Manufacturer: Schneider Electric
Series: Modicon Quantum (140 Series)
Module Type: AC Discrete Input Module
Channels: 32 points (2 input words)
Form Factor: 1 slot, hot‑swappable
Coating: Standard non‑conformal coating
Weight: ~0.34 kg
Application: General factory, machinery, assembly lines, 24 V AC signal monitoring
2. Electrical Specifications
Nominal Input Voltage: 24 V AC
Operating Frequency: 47 … 63 Hz
Logic 1 (ON):
12 … 30 V AC @ 57–63 Hz
14 … 30 V AC @ 47–53 Hz
Logic 0 (OFF):
0 … 6 V AC @ 60 Hz
0 … 5 V AC @ 50 Hz
Input Current: 11.1 … 13.2 mA
Leakage Current: max 1.9 mA
Response Time:
OFF → ON: 0.75 … 4.9 ms
ON → OFF: 7.3 … 12.3 ms
Isolation (Channel‑to‑Bus): 1780 Vrms, 1 minute
Backplane Current: 250 mA
Power Dissipation: 10.9 W max
Internal Power: Powered by Quantum backplane
3. I/O & LED Indicators (Front)
IN0 … IN31 (Green LEDs) – Individual input status (ON = lit)
ACTIVE (Green LED) – Bus communication OK
F (Red LED) – External fault (overvoltage, short circuit)
4. Environmental Specifications
Operating Temperature: 0 °C … +60 °C
Storage Temperature: −40 °C … +85 °C
Relative Humidity: 5% … 95% non‑condensing
Altitude: ≤ 2,000 m (standard) / up to 5,000 m derated
ESD: 4 kV contact / 8 kV air
EMI: 10 V/m (80–2000 MHz)
Protection Class: IP20
5. Physical & Mechanical
Dimensions (W × H × D): 35 × 122 × 52 mm (1 slot)
Mounting: Any single slot, hot‑swap compatible
Wiring: Screw terminals (field side)
Grouping: 4 groups × 8 channels, 4 independent commons
Field Wire Size: 0.5 … 2.5 mm²
6. Wiring & Connection
Common: One common per 8 channels (4 commons total)
Input: Apply 24 V AC between common and input terminal
Shielding: Recommended for long cables; ground at one end only
7. Software Configuration
Unity Pro (recommended)
Concept v2.2+
ProWORX 32
Add 140DAI35300 (1 slot) to I/O map
Default input address: %I0 … %I31 (2 words)
Set input filter (software, optional)
Download to CPU
8. Troubleshooting
All IN LEDs OFF: Check 24 V AC supply and common wiring
F (Red) ON: Overvoltage, short circuit, or wiring fault
ACTIVE OFF: Module not recognized; reseat or check backplane
Erratic Inputs: Poor grounding, noise, or loose terminals
9. Certifications
CE (EN 55011, EN 61131‑2)
UL 508 / CSA C22.2 No. 142
CUL, FM Class I Div 2
RoHS compliant
10. Ordering Information
140DAI35300: Standard non‑coated (general environment)
140DAI35300C: Conformal coated (harsh environment)
Get a Quote