140DAI34000
140DAI34000
Modicon Quantum Discrete Input Module
Description
140DAI34000
Modicon Quantum 16 Channels 24V AC Discrete Input Module
English Specification Manual
1. General Information
Part Number: 140DAI34000Manufacturer: Schneider ElectricSeries: Modicon QuantumModule Type: AC Digital Input ModuleChannel Quantity: 16 pointsInstallation: Single slot, hot swappableCoating: Standard non-conformal coatingWeight: Approx 0.3kgApplication: Industrial field 24V AC signal collection, switch status monitoring
2. Electrical Parameters
Rated Input Voltage: 24V ACWorking Frequency Range: 47Hz ~ 63HzLogic ON Voltage Range: 16~30V AC(60Hz), 18~30V AC(50Hz)Logic OFF Voltage Range: 0~6V AC(60Hz), 0~5V AC(50Hz)Typical Input Current: 12mA@60Hz, 10.7mA@50HzResponse TimeOFF to ON: 0.75~4.9msON to OFF: 7.3~12.3msIsolation Voltage: 1780Vrms 1 minute between channel and busBackplane Current Consumption: 180mAMax Power Consumption: 5.5WInternal Power Supply: Powered by PLC backplane
3. Terminal Definition
Internal grouping: Two groups, 8 channels per groupCommon terminal design: Independent common terminal for each groupField wiring mode: Screw terminal wiringWiring method: Connect 24V AC power between common terminal and input signal terminal
4. Indicator Function
IN0~IN15 Green LED: Corresponding channel input status, light on means signal inputACTIVE Green LED: Module normal communication with backplaneF Red LED: External circuit fault, overvoltage or short circuit alarm
5. Environmental Parameters
Operating Temperature: 0℃ ~ +60℃Storage Temperature: -40℃ ~ +85℃Relative Humidity: 5%~95% non-condensingMax Working Altitude: 2000mAnti-electrostatic: 4kV contact discharge, 8kV air dischargeElectromagnetic Anti-interference: Meet industrial EMC standardProtection Grade: IP20
6. Installation Instructions
Cut off PLC rack power supply before installation
Insert the module into any single slot of Quantum backplane and lock tightly
Field signal wiring shall be firm and avoid virtual connection
Long-distance signal cables are recommended to use shielded cables with single-point grounding
7. Software Configuration
Applicable programming software: Unity Pro, Concept, ProWORX 32
Add 140DAI34000 module in hardware configuration
Default input address range: %I0 ~ %I15
Set software input filter time as required
Compile and download configuration program to PLC CPU
8. Fault Diagnosis
All input indicators not lit: Check external 24V AC power supply and common line wiringFault red light always on: External circuit short circuit, overvoltage or wiring errorCommunication indicator off: Module loose insertion or backplane failureSignal jump unstable: Poor field grounding or strong electromagnetic interference
9. Certification Standard
CE certification, UL508, CSA C22.2 No.142FM Class I Division 2 hazardous area certificationRoHS environmental protection compliant
10. Model Classification
140DAI34000: Standard non-coated version140DAI34000C: Conformal coated version for harsh environment
Get a Quote