140CRP81100
Description
140CRP81100
Modicon Quantum PROFIBUS‑DP Master Head Module
Instruction Sheet (English, Full Manual Style)
1. General Description
Manufacturer: Schneider Electric
Series: Modicon Quantum (140 Series)
Module Type: PROFIBUS‑DP Master Head (RIO Master)
Form Factor: Single slot, hot‑swap
Coating: Non‑coated (standard industrial)
Weight: approx. 0.45 kg
2. Specifications
2.1 Electrical
Backplane Voltage: 24 VDC (20 … 30 VDC)
Backplane Current: 1.2 A
Power Dissipation: 6.5 W
Isolation: PROFIBUS / RS‑232 isolated from PLC backplane
Fuse Recommendation: 2 A slow‑blow
2.2 PROFIBUS‑DP Interface (DB9 Male)
Protocol: PROFIBUS‑DP V0 / V1 (Master)
Baud Rate: 9.6 kbps … 12 Mbps
Max Slaves: 31 DP slaves per master
I/O Size per Slave: up to 128 In / 128 Out words
Topology: Multidrop line, repeaters allowed
Termination: 120 Ω at both ends of the line
Cable: Shielded twisted pair (PROFIBUS DP cable)
2.3 RS‑232 Interface (DB9 Male)
Protocol: Modbus RTU, ASCII, or user‑defined
Baud Rate: 300 … 115.2 kbps
Data Format: 7/8 data bits, 1 stop bit, parity (None/Odd/Even)
2.4 Environmental
Operating Temperature: 0 °C … +60 °C
Storage Temperature: −40 °C … +85 °C
Relative Humidity: 5 % … 95 % non‑condensing
Altitude: ≤ 2,000 m
ESD: 4 kV contact / 8 kV air
EMI: 10 V/m (80–2000 MHz)
Protection Class: IP20
2.5 Physical
Dimensions (W × H × D): 57 × 122 × 52 mm (Quantum single slot)
Mounting: Any single slot in Quantum backplane, hot‑swap capable
3. LED Indicators (Front Panel)
PWR (Green) – ON: Module power OK
RUN (Green) – ON: Module active / operational
COM (Green, Blinking) – PROFIBUS communication activity
ERR (Red) – ON/Blink: Fault (comm loss, config error, duplicate address)
4. Installation
Power OFF the Quantum rack before inserting the module (hot‑swap allowed in normal operation).
Insert 140CRP81100 into any single slot; push firmly until latched.
Power ON the rack; verify PWR and RUN LEDs are ON.
5. Wiring & Pinout
5.1 PROFIBUS‑DP (DB9 Male)
| Pin | Signal | Description |
|---|---|---|
| 1 | — | Not used |
| 2 | — | Not used |
| 3 | RxD/TxD+ | Data + |
| 4 | — | Not used |
| 5 | GND | Ground |
| 6 | +5 V | Termination power (optional) |
| 7 | — | Not used |
| 8 | RxD/TxD− | Data − |
| 9 | — | Not used |
Connect shield to protective earth (PE) at one end only.
Enable 120 Ω termination at both physical ends of the PROFIBUS line.
5.2 RS‑232 (DB9 Male)
6. Software Configuration
Unity Pro (recommended)
Concept v2.2+
Modsoft v2.32+
Add module 140CRP81100 to I/O configuration.
Set PROFIBUS parameters: baud rate, master address (0), slave addresses (1–31).
Map DP slave I/O to Quantum memory (%I, %Q, %MW).
Configure RS‑232 port (Modbus RTU/ASCII) if used.
Download configuration to Quantum CPU.
7. Troubleshooting
PWR OFF: Check rack 24 VDC supply; reseat module.
RUN OFF: Configuration missing / invalid; re‑download project.
ERR ON: PROFIBUS short circuit, wrong termination, duplicate slave address, or baud rate mismatch.
COM no blink: No slaves on bus; check cabling and termination.
8. Certifications
CE (EN 55011, EN 61131‑2)
UL 508
CSA C22.2 No. 142
RoHS compliant
Class I Div 2 (hazardous locations)
9. Ordering Information
140CRP81100: PROFIBUS‑DP Master + RS‑232, non‑coated (standard)
140CRP81100C: PROFIBUS‑DP Master + RS‑232, conformal coated (harsh environment)