140CRA93200
May 16, 2026

140CRA93200

140CRA93200 Modicon Quantum S908 RIO Drop Adapter Dual‑Port Redundant Coax, 75Ω, 1.544 Mbps, Non‑Coated

Description

140CRA93200

Modicon Quantum S908 RIO Drop Adapter

Dual‑Port Redundant Coax, 75Ω, 1.544 Mbps, Non‑Coated

English Datasheet / Specification (Full Text)


1. General Information

  • Part Number: 140CRA93200

  • Manufacturer: Schneider Electric

  • Series: Modicon Quantum (140 series)

  • Module Type: S908 RIO Drop Adapter, Dual‑Port Redundant

  • Coating: Standard non‑conformal coated

  • Ports: 2 × RIO (F‑type elbow), NO SAT port

  • Function: Remote I/O drop with redundant S908 coax; connects to RIO head for fault‑tolerant network

  • Platform: Quantum PLC rack, single slot, hot‑swap

  • Application: High‑reliability industrial automation, redundant RIO networks


2. Key Difference vs. 140CRA931xx

  • 140CRA93100/00C: Single RIO port, no SAT / coated

  • 140CRA93101/01C: Single RIO + SAT port, standard / coated

  • 140CRA93200: Dual RIO ports (redundant), no SAT, non‑coated


3. Electrical Specifications

  • Backplane Voltage: 24 VDC (20 … 30 VDC)

  • Backplane Current: 750 mA (2 channels)

  • Power Dissipation: 3.8 W (2 channels)

  • Isolation: 500 VDC (coax center ↔ ground)

  • Dynamic Range: 35 dB

  • Recommended Fuse: 1 A slow‑blow


4. Communication (S908 Redundant RIO)

  • Protocol: S908 (Quantum proprietary RIO)

  • Speed: 1.544 Mbps (fixed)

  • Ports:

    • 2 × S908 RIO: F‑type female, 75Ω, elbowed (redundant A/B)

  • Cable: 75Ω coaxial (Belden 9182 or equivalent)

  • Topology: Redundant multidrop (A/B buses)

  • Max Distance: 1,500 m (single segment, no repeaters)

  • Max Drops: 31 drops per RIO head

  • I/O per Drop: 128 In / 128 Out words

  • Termination: 75Ω at first/last drop on both A and B buses


5. Environmental Specifications

  • Operating Temperature: 0 °C … +60 °C

  • Storage Temperature: −40 °C … +85 °C

  • Relative Humidity: 5% … 95% non‑condensing

  • Altitude: ≤ 5,000 m

  • Shock/Vibration: Industrial standard

  • ESD: 4 kV contact / 8 kV air

  • EMI: 10 V/m (80–2000 MHz)

  • Conformal Coating: No (standard)


6. Physical & Mechanical

  • Dimensions: Quantum single slot (57 × 122 × 52 mm)

  • Mounting: Hot‑swap, any single slot

  • Weight: ~0.51 kg

  • LED Indicators:

    • PWR (Green): Power OK

    • RUN (Green): Module active

    • COM (Green Blink): S908 communication

    • ERR (Red): Fault (comm loss / address conflict / config error)


7. Installation & Wiring

  1. Power OFF rack before insertion; hot‑swap capable in normal operation.

  2. Connect RIO A and RIO B to redundant S908 network (75Ω coax).

  3. Shield grounding: Single‑point at RIO head end.

  4. Address setting: Rotary switch 1–31.

  5. Termination: 75Ω at both ends of trunk on both A and B buses.


8. Software Configuration

  • Software: Unity Pro

  • Add model: 140CRA93200

  • Set drop address (1–31) matching rotary switch

  • Enable redundant RIO (A/B) in configuration

  • Map I/O words to Quantum memory

  • Download configuration to CPU


9. Certifications

  • CE (EN 55011, EN 61131‑2)

  • UL 508, CSA C22.2 No.142

  • RoHS compliant

  • Class I Div 2 (hazardous areas)


10. Ordering Reference (RIO Drop Family)

  • 140CRA93100: Single RIO, no SAT, non‑coated

  • 140CRA93100C: Single RIO, no SAT, coated

  • 140CRA93101: Single RIO + SAT, non‑coated

  • 140CRA93101C: Single RIO + SAT, coated

  • 140CRA93200: Dual RIO (redundant), no SAT, non‑coated


Get a Quote