140CRA93101C
Description
140CRA93101C
Modicon Quantum S908 RIO Drop Adapter (Conformal Coated)
Single‑Cable S908 RIO + SAT Port, 75Ω Coax, 1.544 Mbps
English Datasheet / Specification (Full Text)
1. General Information
Part Number: 140CRA93101C
Manufacturer: Schneider Electric
Series: Modicon Quantum (140 series)
Module Type: S908 RIO Drop Adapter (Slave) + SAT Port
Coating: Conformal Coated (三防涂覆 / 防潮防霉防盐雾)
Function: Connect remote I/O racks to Quantum S908 RIO network; SAT port for satellite daisy‑chain expansion
Platform: Quantum PLC racks, hot‑swap single slot
Application: Industrial automation, harsh environment (humidity, dust, mild corrosive)
2. Key Difference vs. 140CRA93101
140CRA93101: Standard, non‑coated
140CRA93101C: Conformal coated (same electrical/communication specs, better environmental resistance)
3. Electrical Specifications
Backplane Voltage: 24 VDC (20 … 30 VDC)
Backplane Current: 600 mA
Power Dissipation: 3 W
Isolation: 500 VDC (coax center ↔ ground)
Dynamic Range: 35 dB
Recommended Fuse: 1 A slow‑blow
4. Communication (S908 RIO + SAT)
Protocol: S908 (Quantum proprietary RIO)
Speed: 1.544 Mbps (fixed)
Ports:
1 × S908 RIO: F‑type female, 75Ω, elbowed
1 × SAT (Satellite): F‑type female, 75Ω
Cable: 75Ω coaxial (Belden 9182 or equivalent)
Topology: Multidrop + satellite expansion
Max Distance: 1,500 m (single segment, no repeaters)
Max Drops: 31 drops per RIO head
I/O per Drop: 128 In / 128 Out words
Termination: 75Ω at first/last drop (RIO & SAT)
5. Environmental (Coated Version Enhanced)
Operating Temperature: 0 °C … +60 °C
Storage Temperature: −40 °C … +85 °C
Relative Humidity: 5% … 95% non‑condensing
Altitude: ≤ 5,000 m
Shock/Vibration: Industrial standard
ESD: 4 kV contact / 8 kV air
EMI: 10 V/m (80–2000 MHz)
Conformal Coating: Yes (moisture, dust, mild corrosion protection)
6. Physical & Mechanical
Dimensions: Quantum single slot (57 × 122 × 52 mm)
Mounting: Hot‑swap, any single slot
Weight: ~0.51 kg
LED Indicators:
PWR (Green): Power OK
RUN (Green): Module active
COM (Green Blink): S908 communication
ERR (Red): Fault (comm loss / address conflict / config error)
7. Installation & Wiring
Power OFF rack before insertion; hot‑swap capable in normal operation.
Connect S908 RIO port to main RIO network (75Ω coax).
Connect SAT port to satellite drops (daisy‑chain).
Shield grounding: Single‑point at RIO head end.
Address setting: Rotary switch 1–31.
Termination: 75Ω at both ends of trunk and SAT branches.
8. Software Configuration
Software: Unity Pro
Add model: 140CRA93101C
Set drop address (1–31) matching rotary switch
Enable SAT port if used
Map I/O words to Quantum memory
Download configuration to CPU
9. Certifications
CE (EN 55011, EN 61131‑2)
UL 508, CSA C22.2 No.142
RoHS compliant
Class I Div 2 (hazardous areas)
10. Ordering Reference (Full Family)
140CRA93100: S908 RIO Drop, no SAT, non‑coated
140CRA93100C: S908 RIO Drop, no SAT, coated
140CRA93101: S908 RIO Drop + SAT, non‑coated
140CRA93101C: S908 RIO Drop + SAT, coated (this model)
Get a Quote