140CRA21120
May 16, 2026

140CRA21120

140CRA21120 Modicon Quantum DIO Drop Interface Module 24 VDC, 2 Redundant Ports, Distributed I/O Adapter

Description

140CRA21120

Modicon Quantum DIO Drop Interface Module

24 VDC, 2 Redundant Ports, Distributed I/O Adapter

1. General Information

  • Part Number: 140CRA21120

  • Manufacturer: Schneider Electric

  • Platform: Modicon Quantum PLC

  • Module Type: DIO (Distributed I/O) Drop Interface

  • Ports: 2 × redundant DIO ports

  • Power Supply: 24 VDC

  • Form Factor: Single slot, standard Quantum backplane

  • Weight: ~0.7 kg

  • Protection: Conformal coating (TC)

  • Status: Active standard product

2. Electrical Specifications

  • Rated Supply Voltage: 24 VDC

  • Operating Voltage Range: 20 … 30 VDC

  • Supply Current (max): 1.6 A @ 24 VDC

  • Inrush Current: 30 A @ 24 VDC

  • Power Dissipation: ~11 W

  • Backplane Output: 5.1 VDC / 3 A nominal

  • Min. Load Current: 0 A

  • Fuse Rating (Recommended): 2.5 A

  • Buffer Time: 1 ms max

  • Protection:

    • Short‑circuit protection

    • Output overvoltage protection

3. I/O Capacity

  • Input Words: 30

  • Output Words: 32

  • Isolation Voltage: 500 VDC (channel‑to‑backplane)

4. Communication

  • Protocol: Modbus‑compatible DIO (Distributed I/O)

  • Ports: 2 × redundant DIO (terminal block)

  • Topology: Point‑to‑point / multidrop / redundant ring

  • Cable: Shielded twisted pair

  • Termination: Software‑selectable TERM

5. Environmental

  • Operating Temperature: 0 °C … +60 °C

  • Storage Temperature: −40 °C … +85 °C

  • Relative Humidity: 5% … 95% non‑condensing

  • Altitude: ≤ 5,000 m

  • Shock/Vibration: Industrial standard

  • ESD Immunity: 4 kV contact / 8 kV air

  • EM Field Immunity: 10 V/m (80–2000 MHz)

6. Physical & Mechanical

  • Dimensions: Standard Quantum single slot

  • Mounting: Quantum backplane (hot‑swap capable)

  • LED Indicators:

    • PWR: Green = Power OK

    • COM: Green blinking = Communication active

    • ERR: Red = Fault (comm loss / config error)

    • PORT1 / PORT2: Link status

7. Installation & Wiring

7.1 Mounting

  1. Power OFF the Quantum rack.

  2. Insert module into any single‑slot position.

  3. Latch and tighten screw.

7.2 Power Wiring (24 VDC)

  • +24 V: Positive

  • 0 V: Ground

  • PE: Protective Earth

  • Wire size: 0.75–2.5 mm²

7.3 DIO Communication Wiring

  • Connect shielded twisted pair to PORT1 / PORT2.

  • Shield: Ground at one end only (PE).

  • Redundant mode: Both ports connected to separate bus segments.

8. Configuration (Unity Pro)

  1. Add 140CRA21120 in hardware catalog.

  2. Set DIO address (1–63).

  3. Enable redundancy (PORT1 + PORT2).

  4. Assign I/O map: 30 In / 32 Out words.

  5. Download configuration to PLC.

9. Operation & LED Status

  • PWR ON: Module powered.

  • COM Blinking: Data exchange active.

  • ERR Steady Red: Communication loss / remote drop fault.

  • ERR Flashing: Address conflict / config mismatch.

  • PORT1/PORT2 Green: Link up.

10. Certifications

  • CE

  • UL 508

  • CSA C22.2 No.142 / Class 1 Div 2

  • C‑Tick, DNV, GOST

  • RoHS compliant

11. Ordering Info

  • 140CRA21120: Standard, 24 VDC, 2 redundant DIO ports


Get a Quote