140CRA21120
Description
140CRA21120
Modicon Quantum DIO Drop Interface Module
24 VDC, 2 Redundant Ports, Distributed I/O Adapter
1. General Information
Part Number: 140CRA21120
Manufacturer: Schneider Electric
Platform: Modicon Quantum PLC
Module Type: DIO (Distributed I/O) Drop Interface
Ports: 2 × redundant DIO ports
Power Supply: 24 VDC
Form Factor: Single slot, standard Quantum backplane
Weight: ~0.7 kg
Protection: Conformal coating (TC)
Status: Active standard product
2. Electrical Specifications
Rated Supply Voltage: 24 VDC
Operating Voltage Range: 20 … 30 VDC
Supply Current (max): 1.6 A @ 24 VDC
Inrush Current: 30 A @ 24 VDC
Power Dissipation: ~11 W
Backplane Output: 5.1 VDC / 3 A nominal
Min. Load Current: 0 A
Fuse Rating (Recommended): 2.5 A
Buffer Time: 1 ms max
Protection:
Short‑circuit protection
Output overvoltage protection
3. I/O Capacity
Input Words: 30
Output Words: 32
Isolation Voltage: 500 VDC (channel‑to‑backplane)
4. Communication
Protocol: Modbus‑compatible DIO (Distributed I/O)
Ports: 2 × redundant DIO (terminal block)
Topology: Point‑to‑point / multidrop / redundant ring
Cable: Shielded twisted pair
Termination: Software‑selectable TERM
5. Environmental
Operating Temperature: 0 °C … +60 °C
Storage Temperature: −40 °C … +85 °C
Relative Humidity: 5% … 95% non‑condensing
Altitude: ≤ 5,000 m
Shock/Vibration: Industrial standard
ESD Immunity: 4 kV contact / 8 kV air
EM Field Immunity: 10 V/m (80–2000 MHz)
6. Physical & Mechanical
Dimensions: Standard Quantum single slot
Mounting: Quantum backplane (hot‑swap capable)
LED Indicators:
PWR: Green = Power OK
COM: Green blinking = Communication active
ERR: Red = Fault (comm loss / config error)
PORT1 / PORT2: Link status
7. Installation & Wiring
7.1 Mounting
Power OFF the Quantum rack.
Insert module into any single‑slot position.
Latch and tighten screw.
7.2 Power Wiring (24 VDC)
+24 V: Positive
0 V: Ground
PE: Protective Earth
Wire size: 0.75–2.5 mm²
7.3 DIO Communication Wiring
Connect shielded twisted pair to PORT1 / PORT2.
Shield: Ground at one end only (PE).
Redundant mode: Both ports connected to separate bus segments.
8. Configuration (Unity Pro)
Add 140CRA21120 in hardware catalog.
Set DIO address (1–63).
Enable redundancy (PORT1 + PORT2).
Assign I/O map: 30 In / 32 Out words.
Download configuration to PLC.
9. Operation & LED Status
PWR ON: Module powered.
COM Blinking: Data exchange active.
ERR Steady Red: Communication loss / remote drop fault.
ERR Flashing: Address conflict / config mismatch.
PORT1/PORT2 Green: Link up.
10. Certifications
CE
UL 508
CSA C22.2 No.142 / Class 1 Div 2
C‑Tick, DNV, GOST
RoHS compliant
11. Ordering Info
140CRA21120: Standard, 24 VDC, 2 redundant DIO ports
Get a Quote