140CPS52400
May 16, 2026

140CPS52400

Schneider Electric 140CPS52400 Modicon Quantum – 5.1 VDC Backplane Power Supply (8 A Redundant / Summable, 100–150 VDC Input, Non‑Coated, No Alarm Contact)

Description

施耐德16.jpg

Schneider Electric

140CPS52400

Modicon Quantum – 5.1 VDC Backplane Power Supply

(8 A Redundant / Summable, 100–150 VDC Input, Non‑Coated, No Alarm Contact)

1. General Information

  • Manufacturer: Schneider Electric

  • Part Number: 140CPS52400

  • Series: Modicon Quantum PLC

  • Type: Rack‑mount backplane power supply (redundant / summable)

  • Input: 100–150 VDC (nominal 125 VDC)

  • Output: 5.1 VDC (logic power for Quantum backplane)

  • Application: Quantum racks with 125 VDC plant supply; large/heavy‑load racks; supports 1+1 redundancy and parallel summing (up to 2 units → 16 A)

  • Coating: Non‑coated (standard)

  • Key Trait: Redundancy capable (1+1), no alarm contact

  • “C” version: 140CPS52400C = conformal coated


2. Electrical Specifications

Input (DC)

  • Voltage: 100–150 VDC (nominal 125 VDC)

  • Input Current: 0.5 A @ 125 VDC

  • Inrush Current: 28 A max @ 125 VDC

  • Hold‑up Time: ≤ 1 ms @ 125 VDC

  • External Fuse: 2 A time‑lag (slow‑blow)

Output

  • Voltage: 5.1 VDC ±1% (regulated)

  • Current (@60°C): 0.5–8 A continuous (redundant / summable)

  • Redundancy: Supported (1+1 mode) (two units for full redundancy)

  • Total Parallel Current: Up to 16 A (2 × 8 A modules, summable only)

  • Ripple & Noise: < 50 mVpp typical

  • Protection: OVP / OLP / SCP / thermal shutdown (all internal)

  • Power Dissipation: 6 + (1.5 × Iout) W (Iout in A)

  • Efficiency: ≥ 85% typical

Signaling & Alarm

  • Local Indication: Green “PWR OK” LED

  • Alarm Contact: None (no relay output)


3. Environmental & Mechanical

  • Operating Temperature: 0 °C to +60 °C

  • Storage Temperature: −40 °C to +85 °C

  • Relative Humidity: 95% RH max, non‑condensing

  • Altitude: Up to 5,000 m

  • Protection Class: IP20 (indoor use)

  • Mounting: 1 slot in Quantum backplane; hot‑swappable

  • Dimensions: 103.9 × 40.3 × 250 mm

  • Weight: Approx. 0.65 kg


4. Key Features

  1. 100–150 VDC wide‑range input: for 125V DC industrial systems。

  2. 8A high‑current 5.1 VDC output: for large/heavy‑load Quantum racks。

  3. Redundant (1+1): two units for fault‑tolerant operation。

  4. Summable (2 units max): parallel up to 16 A total。

  5. Basic protection: OVP/OLP/SCP/thermal shutdown。

  6. Green “PWR OK” LED: local status only (no alarm relay)。

  7. Hot‑swappable: replace without rack shutdown。

  8. Non‑coated (standard): for general industrial environments。


5. Certifications

  • CE

  • UL 508

  • CUL / CSA C22.2 No 142

  • FM Class 1 Div 2

  • RoHS compliant


6. Ordering Notes

  • 140CPS52400: 100–150 VDC, 8 A redundant/summable, non‑coated, no alarm contact

  • Compare to 140CPS52400C: 52400 = non‑coated; 52400C = conformal coated。

  • Compare to 140CPS51100/51100C: 52400 = 8A redundant; 51100 = 3A non‑redundant

  • Compare to 140CPS2xxx/4xxx: 52400 = 125V input; 2xxx=24V; 4xxx=48V。


Get a Quote