CFP-RTD-122
Description
I. Basic Information
Model: CFP-RTD-122 (cFP-RTD-122)
Manufacturer: National Instruments (NI)
Series: Compact FieldPoint (cFP)
Status: Obsolete
Location: High-precision 8-channel temperature/resistance acquisition, compatible with industrial platinum resistance
Part Number: 777318-12
II. Core Specifications (Channels / Electrical)
Number of channels: 8 single-ended inputs (supporting 2/3-wire RTD)
RTD type: Pt100 (100Ω), Pt1000 (1000Ω) platinum resistance
TCR (α): Built-in 6 linearizations (3850/3902/3916/3928/3981/4280 ppm/°C)
Measurement range:
Temperature: -200 °C ~ +850 °C (Pt100)
Resistance: 0–400 Ω / 0–4000 Ω (direct resistance measurement)
Resolution: 16 bits (0.015 Ω @ 400Ω range)
Excitation current: 0.25 mA pulse constant current per channel
Compensation method: True 3-wire compensation (eliminating lead resistance error)
Filtering: 50/60 Hz noise suppression (common mode / differential mode)
Isolation: 2300 Vrms transient overvoltage protection (channel - backplane)
Accuracy: ±0.05 °C (typical, Pt100 @ 25 °C)
Update rate: 10 Hz (all channels)
III. Wiring and Base
Required base: CFP-CB-1 (36-pin terminal block)
Wiring terminals (per channel):
EX+: Excitation positive
SENSE: Measurement end
COM: Common end
RTD wiring compatibility:
3-wire: EX+, SENSE, COM (recommended, highest accuracy)
2-wire: SENSE and COM shorted
4-wire: Optional 3-wire connection, remaining 1 wire open
IV. Mechanical and Environment
Size: 127 × 66 × 24 mm (standard cFP module)
Weight: Approximately 180 g
Installation: cFP-BP-4 / BP-8 backplane, hot pluggable (HotPnP)
Operating temperature: -40 °C ~ +70 °C
Storage temperature: -55 °C ~ +85 °C
Humidity: 10%–90% RH, no condensation
V. Compatibility
Backplane: cFP-BP-4 (4 slots), cFP-BP-8 (8 slots)
Controller: cFP-180x / 2000 / 2100 series
Software: LabVIEW, FieldPoint Explorer, Modbus RTU/TCP
VI. End-of-Production Replacement (Direct Replacement)
Recommended replacement: NI-9217 (C series, 8-channel RTD, 3-wire, 16-bit, isolated, direct replacement)
Base replacement: NI-9923 (C series universal terminal block)
VII. Typical Applications
Industrial furnaces, oven temperature monitoring
Pt100/Pt1000 temperature measurement in pipelines / tank bodies
High-precision resistance sensor acquisition
Environmental and equipment temperature monitoring system

Get a Quote