CFP-DO-400
Description
I. Basic Information
Model: CFP-DO-400 (cFP-DO-400)
Manufacturer: National Instruments (NI)
Series: Compact FieldPoint (cFP)
Part Number: 777318-400
Status: Obsolete (Out of Production)
Location: 8-channel high drive source output, directly drives relays / solenoids / indicator lights
Output Type: Source (anode, high level active)
II. Core Specifications (Electrical / Channels)
Number of channels: 8 independent digital outputs
Output voltage: 5–30 VDC (compatible with 24V industrial standard)
Current per channel: 2 A (maximum), total module current 9 A
Conduction resistance: ≤ 0.3 Ω (low loss)
Logic levels:
ON (high): Output ≈ Vsupply
OFF (low): Output ≈ 0 V
Isolation: 2300 Vrms (channel - backplane isolation, no isolation between channels)
Response time: ≤ 1 μs (high-speed switching)
Update rate: 20 kHz (full channels)
Protection: Reverse polarity protection (±30V), independent overcurrent / short circuit protection per channel
Connector: 68-pin VHDCI female connector (requires CFP-CB-1)
Indicator lights: 1 green LED per channel; 1 green LED for POWER/READY each
III. Mechanical and Environmental
Dimensions: 127 × 66 × 24 mm (standard cFP module)
Weight: Approximately 180 g
Installation: cFP-BP-4 / BP-8 backplane, hot pluggable (HotPnP)
Operating temperature: -40 °C ~ +70 °C
Storage temperature: -55 °C ~ +85 °C
Humidity: 10%–90% RH, no condensation
Vibration: 5 grms (random) / 5 g (sinusoidal), 10–500 Hz
IV. Wiring and Base
Must be paired with: CFP-CB-1 (36-pin universal wiring base)
Wiring specifications: 16–26 AWG copper wire, stripped 6 mm, torque 0.5–0.6 N·m
Power supply: External 5–30 VDC distributed to the module and load via CB-1
V. Compatibility
Backplane: cFP-BP-4 (4 slots), cFP-BP-8 (8 slots)
Controller: cFP-180x / 2000 / 2100 series
Software: LabVIEW, FieldPoint Explorer, Modbus RTU/TCP
VI. Discontinued Replacement (Direct Replacement)
Recommended replacement: NI-9472 (C series, 8-channel 24V Source output, each channel 2A, isolation, direct replacement)
Base replacement: NI-9923 (C series universal terminal base)
VII. Typical Applications
8-channel relay / contactor control
24V solenoid valve, pneumatic valve drive
Indicator lights, buzzer alarm output
Small motor start-stop control
Industrial control cabinet I/O centralized control

Get a Quote