CFP-DI-304
Description
I. Basic Information
Model: CFP-DI-304 (cFP-DI-304)
Manufacturer: National Instruments (NI)
Series: Compact FieldPoint (cFP)
Part Number: 777318-304
Status: Obsolete (Out of Production)
Location: High-density 32-channel 24VDC digital input, suitable for sensors / buttons / relays
Input Type: Sink (Current Sinking, Low Level Active)
II. Core Specifications (Electrical / Channels)
Number of channels: 32 isolated digital inputs
Input voltage: 18–30 VDC (nominal 24V)
Input impedance: 30 kΩ
Logic levels:
ON (high): ≥ 18 VDC
OFF (low): ≤ 5 VDC
Isolation: 250 Vrms (channel - backplane isolation, no isolation between channels)
Transient withstand voltage: 2300 Vrms / 5 seconds
Update rate: 1 kHz (full channel)
Power consumption: Approximately 1 W (powered by backplane)
Connector: 68-pin VHDCI female connector (requires CFP-CB-1 wiring base)
Indicator lights: 1 green LED per channel; 1 green LED for POWER/READY each
III. Mechanical and Environmental
Dimensions: 127 × 66 × 24 mm (standard cFP module)
Weight: Approximately 193 g (6.81 oz)
Installation: cFP-BP-4 / BP-8 backplane, hot-swappable (HotPnP)
Operating temperature: -40 °C ~ +70 °C (vertical); -40 ~ +65 °C (other orientations)
Storage temperature: -55 °C ~ +85 °C
Humidity: 10%–90% RH, no condensation
Vibration: 5 grms (random) / 5 g (sinusoidal), 10–500 Hz
IV. Wiring and Base
Must be paired with: CFP-CB-1 (36-pin universal wiring base)
Wiring specifications: 16–26 AWG copper wire, stripped 6 mm, torque 0.5–0.6 N·m
Power supply: External 24VDC distributed to the module and sensors via CB-1
V. Compatibility
Backplane: cFP-BP-4 (4 slots), cFP-BP-8 (8 slots)
Controller: cFP-180x / 2000 / 2100 series
Software: LabVIEW, FieldPoint Explorer, Modbus RTU/TCP
VI. Discontinued Replacement (Direct Replacement)
Recommended replacement: NI-9425 (C series, 32-channel 24V Sink input, 7 μs high speed, isolation, direct replacement)
Base replacement: NI-9923 (C series universal terminal base)
VII. Typical Applications
32-channel pushbutton / switch / proximity switch input
PLC expansion high-density DI
Production line status monitoring (sensors / relay feedback)
Industrial control cabinet I/O centralized collection

Get a Quote