CFP-AI-111
Description
I. Basic Information
Model: cFP-AI-111 (often written as CFP-AI-111)
Manufacturer: National Instruments (NI)
Series: Compact FieldPoint (cFP) I/O
Status: Obsolete
Alternative Model: NI-9208 (C series, 16 channels, 16-bit current input)
Position: 16-channel 4-20mA transmitter acquisition, high-density analog input for industrial process control
II. Core Specifications (16-channel dedicated current)
Number of channels: 16 single-ended analog current inputs
Resolution: 16-bit ADC
Total update rate: 360 Hz (for all channels)
Input range (software selectable):
4–20 mA (most commonly used) 0–20 mA
±20 mA
Accuracy: ±(0.05% reading + 0.05% range)
Input impedance: 5 Ω (for current loop)
Filter (optional per channel): 50 Hz / 60 Hz / 500 Hz (anti-power frequency interference)
Isolation: Channel isolated from the backplane, no inter-channel isolation
Overvoltage protection: 2300 V transient peak (I/O – bus)
Diagnosis: Open circuit / short circuit detection, overrange alarm, onboard linearization
III. Environment and Mechanics
Operating temperature: -40 °C ~ +70 °C (industrial wide temperature range)
Humidity: 10%–90% RH, no condensation
Dimensions: 92 × 60 × 20 mm
Weight: Approximately 115 g
Installation: cFP-BP-4 / BP-8 backplane, hot-swappable
Terminal base: FP-TB-10 (16-pin current-specific)
IV. cFP-AI-100 vs cFP-AI-111 (Key Differences) Table
Comparison item cFP-AI-100 cFP-AI-111
Number of channels 8 channels 16 channels (doubled density)
Resolution 12 bits 16 bits (higher precision)
Signal type Voltage + Current Pure Current (4-20mA optimized)
Filter Fixed 50/60/500Hz selectable
Typical application Mixed signal, small-scale Large-scale 4-20mA transmitter cluster
Replacement for discontinuation NI-9207 NI-9208
V. Typical application scenarios
Process control high-density acquisition: 16 channels of pressure, flow, level, temperature (4-20mA transducer)
Chemical / water treatment: Multi-parameter monitoring (pH, conductivity, dissolved oxygen)
Energy management: Pulse / analog quantity acquisition of electricity meters, water meters, gas meters
Production line monitoring: Centralized collection of signals from multiple workstations
Combined with cFP-2200/2210/2220: Build a 16-32 channel real-time measurement and control system