FBM41A/42C
Description
Foxboro FBM41A / FBM42C (P0902XA‑0C / FBM42C)
60 VDC 8‑Channel Isolated Discrete Input/Output Module
Specifications & User Guide (Copy‑Ready English)
General
Models: FBM41A (P0902XA‑0C) / FBM42C (high‑power variant)
System: Foxboro I/A Series / EcoStruxure Foxboro DCS
Type: 8‑channel galvanically isolated discrete (60 VDC) I/O modules
Difference:
FBM41A: 8DI + 8DO, standard‑power outputs
FBM42C: 8DI + 8DO, high‑power outputs (enhanced current rating)
Redundancy: 1:1 hot‑swap redundant capable
Hot Swap: Supported (no system shutdown)
Certification: CE, UL, CSA, ATEX; Class I Div 2 / Zone 2
Environment: Class G3 (harsh industrial)
Operating Temp: 0 °C to +60 °C
Storage Temp: −40 °C to +85 °C
Humidity: 5–95 % non‑condensing
Enclosure: Die‑cast aluminum, IP20 rated
Dimensions: 140 mm × 165 mm × 45 mm
Weight: 0.68 kg (FBM41A); 0.75 kg (FBM42C)
Common I/O Specifications
Configuration: 8DI + 8DO (channel‑to‑channel & channel‑to‑ground isolated)
Isolation: 600 VAC (1 min)
Status LEDs: 8 channel (ON/FAULT) + module RUN/FAULT
Termination: P0500RY / RH914TG TA (order separately)
Discrete Inputs (8 channels, both models)
Signal Type: Voltage monitor (15–60 VDC)
On‑State: 15–60 VDC; Off‑State: 0–5 VDC
Input Current: 2–6 mA @ 24 VDC
Debounce: Configurable (4 / 8 / 16 / 32 ms)
Open‑Circuit Voltage: 24 VDC ±20 %
Short‑Circuit Current: ≤5 mA
Discrete Outputs (8 channels)
FBM41A (Standard)
Type: Solid‑state switch (external ≤60 VDC)
Rating: 0.25 A / channel; 2 A total max
On‑Resistance: ≤1 kΩ
Off‑Leakage: ≤0.25 mA
Overload Protection: Per channel, auto‑recovery
FBM42C (High‑Power)
Type: High‑current solid‑state switch (external ≤60 VDC)
Rating: 2.5 A / channel; 15 A total max (upgraded from FBM42A)
On‑Resistance: ≤0.3 Ω @ 1 A
Off‑Leakage: ≤0.5 mA
Short‑Circuit Handling: 1‑s shutdown on overload; enhanced thermal dissipation
Power
Supply: 24 VDC (±5 % / −10 %), redundant
Consumption:
FBM41A: 9 W (single); 14 W (redundant)
FBM42C: 13 W (single); 19 W (redundant)
Heat Dissipation:
FBM41A: 8.5 W (single); 13 W (redundant)
FBM42C: 12.2 W (single); 18 W (redundant)
Communication
Fieldbus: Redundant 2 Mbps backplane (I/A Series)
Protocol: Foxboro proprietary
Data Update: 50 ms (default)
Typical Applications
FBM41A: Standard 24–60 VDC on/off control (solenoids, motor starters, contactors); status monitoring (limit/pressure switches).
FBM42C: Heavy‑duty 60 VDC loads (large solenoids, DC motors, heaters, motorized valves); high‑current process skids and legacy system migration.
Key Differences Summary
FBM41A: 0.25 A/channel, 2 A total; general‑purpose, cost‑effective.
FBM42C: 2.5 A/channel, 15 A total; high‑power, heavy loads, upgraded from FBM42A.

Get a Quote