FBM41
May 13, 2026

FBM41

Foxboro FBM41 (P0400YE) – 60 VDC 8‑Channel Isolated Discrete Input/Output Module Specifications & User Guide (Copy‑Ready English) General Model: FBM41 (P0400YE) System: Foxboro I/A Series / EcoStruxure Foxboro DCS Type: 8‑channel isolated discrete (dry contact / 60 VDC) input/output module Function: On‑off control for valves, motors, solenoids, and status sensing Redundancy: 1:1 hot‑swap redundant capable Hot Swap: Supported (no system shutdown) Certification: CE, UL, CSA, ATEX; Class I Div 2 / Zone 2 Environment: Class G3 (harsh industrial) Operating Temp: 0 °C to +60 °C Storage Temp: −40 °C to +85 °C Humidity: 5–95 % non‑condensing Enclosure: Die‑cast aluminum, IP20 rated Dimensions: 140 mm × 165 mm × 45 mm Weight: 0.65 kg I/O Channel Specifications Configuration: 8DI / 8DO (galvanically isolated, channel‑to‑channel & channel‑to‑ground) Discrete Inputs (8 channels) Signal Type: Dry contact / 15–60 VDC sense On‑State: 15–60 VDC; Off‑State: 0–5 VDC Input Current: 1.4 mA typical @ 5–60 VDC Debounce: Configurable (0 / 4 / 8 / 16 / 32 ms) Isolation: 600 VAC (1 min) channel‑to‑channel & channel‑to‑ground Discrete Outputs (8 channels) Type: Solid‑state switch (external source, ≤60 VDC) Rating: 0.25 A / channel (max 2 A total per module) On‑Resistance: ≤1 kΩ; Off‑Leakage: ≤0.25 mA Overload Protection: Per channel, auto‑recovery Isolation: 600 VAC (1 min) channel‑to‑channel & channel‑to‑ground Status LEDs: 8 channel (ON/FAULT) + module RUN/FAULT Termination: P0500RY / RH914TG series TA (order separately)

Description

Foxboro FBM41 (P0400YE) – 60 VDC 8‑Channel Isolated Discrete Input/Output Module

Specifications & User Guide (Copy‑Ready English)

General

Model: FBM41 (P0400YE)

System: Foxboro I/A Series / EcoStruxure Foxboro DCS

Type: 8‑channel isolated discrete (dry contact / 60 VDC) input/output module

Function: On‑off control for valves, motors, solenoids, and status sensing

Redundancy: 1:1 hot‑swap redundant capable

Hot Swap: Supported (no system shutdown)

Certification: CE, UL, CSA, ATEX; Class I Div 2 / Zone 2

Environment: Class G3 (harsh industrial)

Operating Temp: 0 °C to +60 °C

Storage Temp: −40 °C to +85 °C

Humidity: 5–95 % non‑condensing

Enclosure: Die‑cast aluminum, IP20 rated

Dimensions: 140 mm × 165 mm × 45 mm

Weight: 0.65 kg

I/O Channel Specifications

Configuration: 8DI / 8DO (galvanically isolated, channel‑to‑channel & channel‑to‑ground)

Discrete Inputs (8 channels)

Signal Type: Dry contact / 15–60 VDC sense

On‑State: 15–60 VDC; Off‑State: 0–5 VDC

Input Current: 1.4 mA typical @ 5–60 VDC

Debounce: Configurable (0 / 4 / 8 / 16 / 32 ms)

Isolation: 600 VAC (1 min) channel‑to‑channel & channel‑to‑ground

Discrete Outputs (8 channels)

Type: Solid‑state switch (external source, ≤60 VDC)

Rating: 0.25 A / channel (max 2 A total per module)

On‑Resistance: ≤1 kΩ; Off‑Leakage: ≤0.25 mA

Overload Protection: Per channel, auto‑recovery

Isolation: 600 VAC (1 min) channel‑to‑channel & channel‑to‑ground

Status LEDs: 8 channel (ON/FAULT) + module RUN/FAULT

Termination: P0500RY / RH914TG series TA (order separately)

Power

Supply: 24 VDC (±5 % / −10 %), redundant

Consumption: 9 W (single); 14 W (redundant pair)

Heat Dissipation: 8.5 W (single); 13 W (redundant pair)

Communication

Fieldbus: Redundant 2 Mbps backplane (I/A Series)

Protocol: Foxboro proprietary

Data Update: 50 ms (default)

Basic Installation & Usage

Mounting

Snap into standard I/A Series DIN rail or baseplate.

Secure latch; ensure full seating for backplane contact.

Wiring

Connect field devices (contact sensors, solenoids, relays) to TA.

DI: Dry contact or 15–60 VDC; common ground not required (isolated).

DO: External 12–60 VDC source; positive to load, negative to module.

Use shielded twisted pair; separate analog/digital cables.

Wiring size: 0.2–4 mm² (24–12 AWG); ferrules recommended.

Configuration (I/A Series Software)

Set DI debounce time and alarm thresholds.

Configure DO failsafe state (hold / ON / OFF).

Enable diagnostics (open load, short circuit, overcurrent).

Assign redundancy role (primary/secondary) if applicable.

Operation

RUN (green): module ok; FAULT (red): error (comms/power/channel).

Channel LED: ON = active; FLASH = fault (short/open/overload).

Monitor DI status and DO commands in HMI.

Maintenance

Hot‑swap faulty module (no shutdown; TA wiring intact).

Inspect TA wiring, shields, and grounds annually.

Update firmware via I/A Series software.

Calibration: Not required (factory‑calibrated; on‑board diagnostics).

Typical Applications

On/off control for solenoid valves, motor starters, and contactors.

Status monitoring of limit switches, pressure switches, and dry contacts.

Interface to 24–60 VDC discrete devices in process industries.

Migration of legacy FBM03/FBM08 to 200‑series FBMs.

Foxboro27.jpg


Get a Quote