FBM39
May 13, 2026

FBM39

Foxboro FBM39 (P0902UT-0C / P0400YE) – Intelligent Transmitter / 0-20mA Output Interface Module Specifications & User Guide (Copy‑Ready English) General Model: FBM39 (P0902UT‑0C / P0400YE) System: Foxboro I/A Series / EcoStruxure Foxboro DCS Type: Intelligent transmitter interface + 0–20 mA analog output module Function: Connects intelligent transmitters; provides analog output for valves/actuators Redundancy: 1:1 hot‑swap redundant capable Hot Swap: Supported (no system shutdown) Certification: CE, UL, CSA, ATEX; Class I Div 2 / Zone 2 Environment: Class G3 (harsh industrial) Operating Temp: 0 °C to +60 °C Storage Temp: −40 °C to +85 °C Humidity: 5–95 % non‑condensing Enclosure: Die‑cast aluminum, IP20 rated Dimensions: 140 mm × 165 mm × 45 mm Weight: 0.68 kg I/O & Interface Specifications Channels: 8 galvanically isolated (mix of intelligent input / analog output) Signal Types: Intelligent transmitter input (digital + 4–20 mA HART) Analog output: 0–20 mA (configurable for 4–20 mA) Resolution: 13‑bit (AO); 16‑bit (AI) Accuracy: ±0.05 % FS (AO); ±0.02 % FS (AI) Isolation: 600 VAC (1 min) channel‑to‑channel & channel‑to‑ground Load Resistance (AO): 0–750 Ω (20 mA @ 18 VDC compliance) Short‑circuit & Overload Protection: Per channel (auto‑recovery) Status LEDs: 8 channel (ON/FAULT/HART) + module RUN/FAULT Termination: P0500RY terminal plug (included)

Description

Foxboro FBM39 (P0902UT-0C / P0400YE) – Intelligent Transmitter / 0-20mA Output Interface Module

Specifications & User Guide (Copy‑Ready English)

General

Model: FBM39 (P0902UT‑0C / P0400YE)

System: Foxboro I/A Series / EcoStruxure Foxboro DCS

Type: Intelligent transmitter interface + 0–20 mA analog output module

Function: Connects intelligent transmitters; provides analog output for valves/actuators

Redundancy: 1:1 hot‑swap redundant capable

Hot Swap: Supported (no system shutdown)

Certification: CE, UL, CSA, ATEX; Class I Div 2 / Zone 2

Environment: Class G3 (harsh industrial)

Operating Temp: 0 °C to +60 °C

Storage Temp: −40 °C to +85 °C

Humidity: 5–95 % non‑condensing

Enclosure: Die‑cast aluminum, IP20 rated

Dimensions: 140 mm × 165 mm × 45 mm

Weight: 0.68 kg

I/O & Interface Specifications

Channels: 8 galvanically isolated (mix of intelligent input / analog output)

Signal Types:

Intelligent transmitter input (digital + 4–20 mA HART)

Analog output: 0–20 mA (configurable for 4–20 mA)

Resolution: 13‑bit (AO); 16‑bit (AI)

Accuracy: ±0.05 % FS (AO); ±0.02 % FS (AI)

Isolation: 600 VAC (1 min) channel‑to‑channel & channel‑to‑ground

Load Resistance (AO): 0–750 Ω (20 mA @ 18 VDC compliance)

Short‑circuit & Overload Protection: Per channel (auto‑recovery)

Status LEDs: 8 channel (ON/FAULT/HART) + module RUN/FAULT

Termination: P0500RY terminal plug (included)

Power

Supply: 24 VDC (±5 % / −10 %), redundant

Consumption: 11 W (single); 17 W (redundant pair)

Heat Dissipation: 10.5 W (single); 16.2 W (redundant pair)

Communication

Fieldbus: Redundant 2 Mbps backplane (I/A Series)

Protocol: Foxboro proprietary + HART pass‑through

Data Update: 50 ms (default)

HART Support: HART 5/6/7 (per channel)

Basic Installation & Usage

Mounting

Snap into standard I/A Series DIN rail or baseplate.

Secure latch; ensure full seating for backplane contact.

Wiring

Connect intelligent transmitters (pressure/flow/level) and analog devices to P0500RY termination plug.

Transmitter input: 2‑wire (loop‑powered, HART).

Analog output: 2‑wire to valve/actuator; common ground not required (isolated).

Use shielded twisted pair; separate analog/digital cables.

Configuration (I/A Series Software)

Set channel mode: Intelligent Input (HART) / Analog Output (0–20 mA).

Configure AO range (0–20 mA / 4–20 mA) and scaling.

Enable HART (1200 bps); set NE 43 fault thresholds.

Assign failsafe state (hold / 0 % / 100 %) for AO.

Enable diagnostics (short circuit, open load, HART comms).

Operation

RUN (green): module ok; FAULT (red): error (comms/power/channel).

Channel LED: ON = active; FLASH = fault; HART = HART communication.

Monitor HART PV/SV/diagnostics and AO values in HMI.

Maintenance

Hot‑swap faulty module (no shutdown; wiring intact).

Inspect termination plug wiring/shields/grounds annually.

Update firmware via I/A Series software.

Calibration: Not required (factory‑calibrated; on‑board diagnostics).

Typical Applications

Interface for HART intelligent transmitters (pressure/flow/level/temp).

Analog control outputs for valves, actuators, and VFDs.

Mixed intelligent/analog I/O for skids and package units.

Migration of legacy FBM04/FBM05 to 200‑series FBMs.