FBM26
Description
FBM26
General Information
Manufacturer: Foxboro (Schneider Electric)
Model: FBM26
Series: I/A Series DCS
Type: 8‑Input / 8‑Output Isolated Discrete I/O Module
Function: Monitors 125 VDC / dry contact discrete inputs and drives discrete outputs for field devices
Environmental Rating: Class G3 harsh industrial environment (ISA S71.04)
Certification: CE, ATEX, CSA; Class 1 Division 2 / Zone 2 hazardous area approved
Protection Class: IP20
Dimensions (mm): 140 (H) × 165 (W) × 45 (D)
Weight: Approx. 600 g
Key Specifications
Channel Configuration: 8 isolated discrete inputs + 8 isolated discrete outputs
Inputs (8 Channels)
Signal Type: 125 VDC contact sense / dry contact
Logic Levels:
ON: 90–140 VDC
OFF: 0–40 VDC
Isolation: Per‑channel galvanic isolation
Outputs (8 Channels)
Output Ratings (External Powered):
15–60 VDC, up to 2 A per channel
120 VAC / 125 VDC, up to 0.5 A per channel
240 VAC, up to 0.5 A per channel
On‑state Voltage Drop: ≤ 0.2 V @ 2.25 A
Off‑state Leakage Current: ≤ 0.1 mA
General
Module Power: 24 VDC (+5% / −10%)
Power Consumption: ≤ 3 W
Operating Temperature: 0°C to +60°C
Storage Temperature: −40°C to +85°C
Humidity: 5%–95%, non‑condensing
Withstand Voltage: 600 VAC for 1 minute (channel‑to‑ground/channel‑to‑channel)
Main Features
Mixed I/O Design: 8 input + 8 output channels reduce module count and cabinet space。
Per‑Channel Isolation: Galvanic isolation between channels and ground prevents crosstalk。
Multi‑Voltage Outputs: Supports DC and AC loads via external power and termination assemblies (TAs)。
Configurable Operation:
Fail‑safe modes (hold, off, preset)
Sustained or momentary (pulse) outputs
Software‑selectable input debounce filtering
Hot Swappable: Online replacement without system shutdown。
Redundancy Support: 1:1 redundant pairing for high availability。
LED Diagnostics: Front‑panel LEDs for module status and per‑channel indication。
Ladder Logic Support: Executes discrete I/O or ladder logic programs locally。
Applications
Process Industries: Chemical, power, oil & gas, water treatment。
Mixed Discrete I/O: Valve position monitoring + on/off control, limit switches + alarm lights, relay contact monitoring + interlock outputs。
Legacy 125 VDC Systems: Power plants and facilities with 125 VDC control infrastructure。
Harsh & Hazardous Areas: Class G3 environments and Class 1 Div 2/Zone 2 classified locations。