FBM240
May 13, 2026

FBM240

FBM240 (P0927AH) FBM240 is an 8‑Channel Discrete Output + 8‑Channel Readback Input Module by Foxboro (Schneider Electric) for I/A Series/EcoStruxure DCS. Part number P0927AH. It provides redundant, high‑reliability on/off control with output verification. 1. General Information Manufacturer: Foxboro (Schneider Electric) Model: FBM240 (P0927AH) Function: 8‑channel discrete output + 8‑channel voltage readback input (redundant with readback) Mounting: Compact 200 Series field‑mounted; Class G3 (harsh) environments Certifications: CE, ATEX, CSA; Class 1 Division 2 / Zone 2 hazardous areas

Description

FBM240 (P0927AH)

FBM240 is an 8‑Channel Discrete Output + 8‑Channel Readback Input Module by Foxboro (Schneider Electric) for I/A Series/EcoStruxure DCS. Part number P0927AH. It provides redundant, high‑reliability on/off control with output verification.



1. General Information

Manufacturer: Foxboro (Schneider Electric)

Model: FBM240 (P0927AH)

Function: 8‑channel discrete output + 8‑channel voltage readback input (redundant with readback)

Mounting: Compact 200 Series field‑mounted; Class G3 (harsh) environments

Certifications: CE, ATEX, CSA; Class 1 Division 2 / Zone 2 hazardous areas

2. Key Specifications

Channels: 8 isolated discrete outputs, 8 isolated readback inputs

Input (Readback): 15–60 VDC (ON); 0–5 VDC (OFF)

Output Rating:

10 A @ 80–120 VAC

5 A @ 80–125 VDC

5 A @ 15–60 VDCparesource.schneider-electric.com

Isolation: Galvanic isolation per channel

Redundancy: Supports redundant pair operation (1:1)

Filter/Debounce: Configurable (0, 4, 8, 16, 32 ms)

Power: 24 VDC, ≤ 7 W

Operating Temp: -20°C to +70°C

3. Main Features

Output Readback: 8 dedicated inputs verify output state; flags “BAD” if mismatchparesource.schneider-electric.com。

Redundancy Ready: Operates as single or redundant pair for high availabilityparesource.schneider-electric.com。

High‑Power Relays: Switches high‑voltage/current loads (AC/DC)paresource.schneider-electric.com。

Channel Isolation: Per‑channel galvanic isolation reduces crosstalk。

Diagnostics: LED status per channel; fault detection for outputs/inputs。

4. Applications

Used in chemical, power, oil & gas, refining for critical on/off control: motor starters, solenoids, valves, contactors, and relay monitoring in Foxboro DCS environments。

Foxboro26.jpg


Get a Quote