REM615
Description
ABB REM615 Relion® 615 Series
Complete Technical Specification & User Description
General Information
Model: REM615
Series: Relion® 615
Device Type: Motor Protection and Control IED
Manufacturer: ABB
Application: Medium and low voltage asynchronous motors, pumps, fans, conveyors, compressors and industrial motor feeders
Design Form: Withdrawable plug-in unit, 4U panel mounting
Front Protection Degree: IP54
Rear Protection Degree: IP20
Standard Version Configurations
Type AA: 3-phase current + residual current input
Type CA: 3-phase current + residual current + 5-phase voltage input
Power Supply Ratings
Auxiliary AC Supply: 100–240 V AC, 50/60 Hz, operating range 38–110% Un
Auxiliary DC Supply: 24–250 V DC, operating range 80–120% Un
AC Power Consumption: Typical <16 W, Maximum <21 W
DC Power Consumption: Typical <12 W, Maximum <18 W
Analog Inputs
Current Input (CT)
Rated Secondary: 1 A / 5 A selectable
Continuous Current: 20 A
Short Time Withstand: 500 A for 1 second
Voltage Input (VT)
Rated Voltage: 100–120 V
Continuous Withstand: 2 × Un
Optional Analog Modules
Up to 6 channels RTD input (Pt100 / Pt1000)
Up to 2 channels 4–20 mA analog input
Binary Inputs & Outputs
Binary Inputs
Standard: 12 inputs
Optional expandable: 18 inputs
Operating Voltage: 24–250 V DC
Typical Response Time: 3 ms
Binary Outputs
Standard: 10 outputs
Optional expandable: 13 outputs
Rated Voltage: 250 V AC / DC
Continuous Current: 5 A
Environmental Conditions
Operating Temperature: −25 °C to +55 °C
Short-term Temperature: −40 °C to +85 °C (max 16 hours)
Relative Humidity: 5% to 93 %, non-condensing
Maximum Altitude: 4000 m above sea level
Mechanical Data
Dimensions (W × H × D): 180 × 177 × 194 mm
Main Protection Functions
Thermal Overload Protection (49M)
Phase Overcurrent Instantaneous & Time-delayed (50P / 51P)
Earth Fault Protection, Directional / Non-directional (51G / 67N)
Locked Rotor and Motor Stall Protection (51LR / 66)
Phase Unbalance and Loss of Phase Protection (46M)
Overvoltage and Undervoltage Protection (27 / 59)
Motor Start Supervision and Start Blocking
Underload / Loss-of-Load Protection (37)
Optional Arc Flash Protection with high-speed trip ≤ 1 ms
Communication Interfaces & Protocols
Ethernet Interface: 10/100 Base-TX RJ45; optional 100 Base-FX fiber
Supported Protocols:
IEC 61850 (MMS, GOOSE, Sampled Values 9-2 LE)
Modbus TCP / Modbus RTU
DNP3.0 Level 2
Redundancy Support: HSR / PRP (optional)
Time Synchronization: SNTP, IRIG-B, IEEE 1588 PTP v2
Measurement & Recording Functions
Measured Quantities: Phase current, residual current, sequence current; phase voltage, residual voltage, sequence voltage; active power, reactive power, apparent power, power factor, energy
Event Sequence Recording: 100 events with time stamp accuracy ±1 ms
Fault Event Records: Up to 100 fault records
Disturbance Recorder: 4 analog channels + 64 digital channels waveform recording
HMI & Operation
Large graphical LCD display with single-line diagram support
Local control for breaker / switch operation
Embedded web server for remote monitoring and setting
Configuration compatible with ABB PCM600 software
Four-level user access authority: Viewer, Operator, Engineer, Administrator
Key Features
All-in-one protection, control, measurement and monitoring
Withdrawable design for easy replacement and maintenance
Industrial wide temperature and high EMC immunity
Full support for substation automation and network redundancy
Suitable for power plant, chemical, metallurgy, water treatment and industrial distribution systems

Get a Quote