13A0073G08
Description
Model Explanation
13A: Ovation System I/O Series
0073: Function Code (8-channel low-level AI, millivolt level)
G08: Hardware Version (G Series, Version 8, Finalized Stable Version)
Basic Information
Manufacturer: Emerson Process Management
Origin: United States
Form: Standard single-slot card, supports hot swapping
Weight: Approximately 0.38 kg
Installation: Ovation I/O Backplane (Universal for 13A Series)
Certifications: CE, UL/CSA, Class I Div.2
Status: Current mainstream low-level AI spare part, commonly used for power/chemical thermocouple temperature measurement Function positioning
Collect ±20mV low-level signals, compatible with thermocouples (such as K/S type), millivolt-level sensors
8 independent differential inputs, high impedance, strong anti-common-mode interference
13-bit resolution, precise measurement of tiny voltage signals
Channel-level self-diagnosis (open circuit / over-range detection), fault reporting
Software configurable range, supports cold junction compensation (thermocouple)
Designed specifically for low-level weak signals, suitable for high-temperature / high-precision temperature measurement scenarios
Core parameters
Input points: 8 channels (differential)
Input signals: ±20mV (low level, thermocouple / millivolt sensor)
Resolution: 13 bits
Accuracy: ±0.1% full scale
Input impedance: >1MΩ (high impedance, reduces signal attenuation)
Isolation voltage: 1500VAC (channel - system)
Sampling rate: 10 times/second (per channel)
Operating temperature: 0°C ~ +60°C
Power supply: Backplane 5VDC power supply
Power consumption: approximately 3.5W
Adapting accessories
I/O backplane: Ovation 13A series backplane
Terminal unit: 1B30027G01 (8-channel low-level AI dedicated terminal base)
Field cable: Shielded twisted pair (recommended for thermocouple-specific compensation wire)
Compatible modules: Same series analog output, digital I/O cards
Typical applications
Thermal power / gas-fired power plants: Boiler furnace, superheater, reheater thermocouple temperature monitoring
Chemical / oil and gas: Reactor, cracking furnace, heating furnace high-precision temperature measurement
Metallurgy: Steel water temperature, heat treatment furnace temperature, continuous casting temperature monitoring
Paper / pharmaceutical: High-temperature process section, sterilization equipment temperature closed-loop control
Key differences (13A0073G08 vs 13A0072G01)
13A0073G08: 8-channel low-level AI (±20mV), thermocouple-specific, high impedance
13A0072G01: 8-channel standard AO (4-20mA), drives valve / frequency converter, output type
Get a Quote