F8650E
Description
F8650E (HIMA High Performance Secure CPU Module - Wide Temperature Type) Basic Information
Model: F8650E (Part Number: 984865064)
Brand: HIMA (Germany)
Series: HIQuad H51q Safety Instrumentation System (SIS)
Type: Dual CPU Locked-Step Redundant Safety Controller (Wide Temperature Enhanced Version)
Safety Level: IEC 61508 SIL3 (TÜV AK6 Certified)
Installation: 19" Rack, 8SU Width
Status: In Service, One of the Three Models in the F8650 Series (A/E/X)
Hardware Specifications
Processor: 2× Intel 386EX 32-bit, 25MHz, clock synchronization (lockstep redundancy)
Memory (per CPU):
System Flash: 1MB
User Program Flash: 1MB
Data SRAM: 1MB
Dimensions: Approximately 41mm × 187mm × 128mm
Weight: Approximately 0.34kg
Electrical Parameters
Power Supply: 24VDC (18~32VDC, wide voltage range)
Power Consumption: Typical 5W, maximum approximately 6W
Safety Watchdog: 24V output, maximum 500mA, short circuit protection
Communication Interfaces
Serial Port: 2× Isolated RS485, supports Modbus RTU
Backplane Bus: Special I/O bus, connects H51q series I/O modules
Expansion: Supports Profibus DP, Ethernet (optional)
Environmental Parameters (Core Differentiation Points)
Operating Temperature: -40℃ ~ +70℃ (wide temperature range, suitable for extreme environments)
Storage Temperature: -40℃ ~ +85℃
Relative Humidity: 5%~95%, no condensation
Anti-Vibration / Shock: Industrial-grade reinforcement, suitable for outdoor / indoor harsh conditions Core function
Safety logic control: implements ESD emergency stop, BMS burner management, and F&G fire gas interlock.
Dual-machine lock-step redundancy: dual CPUs operate synchronously, real-time comparison is conducted, automatic safe shutdown occurs upon single fault, and there is no single point failure.
Comprehensive hardware self-diagnosis: diagnostic coverage ≥ 99%, monitoring of voltage, temperature, communication, and memory, fault codes are visualized.
Online maintenance: supports hot swapping, the redundant system can be replaced online without interrupting operation.
4-digit diagnostic display: the panel has PWR/RUN/ALM indicator lights + digital tube, which displays the status / address / fault code in real time.

Get a Quote