F8650
Description
F8650 (HIMA Racing Security CPU Module)
Basic Information
Model: F8650 (Common Submodel: F8650X, F8650E)
Brand: HIMA (German Racing Company)
Part Number: F8650X (984865065)
Product Type: Security CPU / Central Processing Module
Applicable Systems: H51q-MS/HS/HRS Safety Instrumentation System (SIS)
Safety Level: IEC 61508 SIL3, TÜV Certification
Architecture: Dual CPU Locked Step Redundancy (Operate synchronously, Fault Self-Detection)
Installation Method: 19" Rack Slot Type (8SU)
Protection Level: IP20
Weight: Approximately 0.5kg
Hardware Specifications
Processor: 2× Intel 386EX 32-bit, 25MHz, clock synchronization
Memory (per CPU):
System Flash: 1MB
User Program Flash: 1MB
Data SRAM: 1MB
Processing Capacity: Supports complex security logic, response time as low as 20ms
Size: Approximately 120mm×99mm×22mm
Electrical Parameters
Power Supply Voltage: 24VDC (18~32VDC)
Power Consumption: Typical 5W
Security Watchdog: 24V output, maximum 500mA, short circuit protection
Communication Interface
Serial Port: 2× Isolated RS485, supports Modbus RTU
Backplane Bus: Special I/O bus, connects HIMA I/O module
Expansion: Supports Profibus DP, Ethernet (optional)
Environmental Parameters
Operating Temperature: -40℃ ~ +70℃ (F8650E) / +85℃ (F8650X)
Storage Temperature: -40℃ ~ +85℃
Relative Humidity: 5%~95%, no condensation Core function
Safety logic control: The core of the SIS system, implementing safety interlocks such as ESD, BMS, F&G, etc.
Dual-machine redundant fault-tolerant: Two CPUs operate synchronously, comparing data in real time, and automatically shutting down in case of faults.
Comprehensive hardware self-diagnosis: Covering voltage, temperature, communication, memory, etc., with diagnostic coverage of ≥ 99%.
Online maintenance: Supports hot swapping, the redundant system can be replaced online without interrupting operation.
4-digit diagnostic display: Real-time display of module status, fault codes, facilitating rapid troubleshooting.
Panel indicator lights and display
PWR (green): Normal power supply
RUN (green): Normal operation (flashing)
ALM (red): Hardware/program failure
4-digit digital tube: Displays diagnostic information, station address, and fault codes