F8627X (HIMA Enhanced Safety Ethernet Communication Module) Basic Information
Model: F8627X
Brand: HIMA (Germany's HIMA)
Type: H41q/H51q System SIL3 Safety Ethernet Communication Module (Enhanced Version)
Safety Level: IEC 61508 SIL3, TÜV Certified
Part Number: 984862765
Installation: 19-inch rack, occupying 1 slot (compatible with F8627)
Protection Level: IP20
Weight: Approximately 0.5kg
Electrical parameters
Power supply: 5VDC (backplane, 2A), 24VDC (system)
Power consumption: Typical 5W, maximum 10W
Insulation withstand voltage: Communication interface to ground 500V AC/1 minute
Built-in protection: Overvoltage, undervoltage, reverse connection, overtemperature, short circuit protection
Hardware performance
Processor: 32-bit secure communication processor, hardware-level fault self-diagnosis
Memory: 4MB Flash (firmware), 8MB SDRAM (data)
Architecture: TMR triple redundancy, dual bus fault tolerance
Diagnostic coverage: ≥99% (link / hardware / protocol fault detection)
Response time: ≤10ms (safe data interaction)
Communication interface
Ethernet: 1×RJ45, 10/100Base-TX (IEEE 802.3)
High-speed serial (HSR): 1×RJ12, redundant module interconnection
Debug port: 1×RS-232 (DB9), local configuration / diagnosis
Protocol support: SafeEthernet, Modbus TCP, OPC DA, OPC A&E, ELOP II
Transmission rate: Ethernet maximum 100Mbps
Environmental parameters
Operating temperature: -20℃ ~ +60℃
Storage temperature: -40℃ ~ +85℃
Relative humidity: 5%~95%, no condensation
Vibration / shock: Compliant with IEC 60068 industrial standards
MTBF: >1,000,000 hours Core function
Multi-protocol Secure Communication: SIL3 SafeEthernet + Open Protocol (Modbus TCP/OPC), multi-purpose in one network
Redundancy and Fault Tolerance: Dual-module / Dual-link redundancy, automatic fault switching, no data loss
Protocol Conversion: Seamless interconnection between HIMA system and DCS/PLC/HMI, supports alarm event upload (OPC A&E)
Real-time Diagnosis: Self-diagnosis of hardware / link / protocol faults, fault reporting does not affect safe operation
Hot Swap: Supports online replacement, automatically synchronizes configuration and status after replacement
Panel Indicators
PWR Green: Power normal, always on
RUN Green: Operation normal, flashing
ALM Red: Hardware / communication fault alarm
ETH Yellow: Ethernet data transmission and reception flashing
HSR Yellow: High-speed serial communication flashing
F8627X vs F8627 (Core Differences)
F8627: Basic version, only supports SafeEthernet, OPC DA; Part Number 984862760
F8627X: Enhanced version, adds Modbus TCP, OPC A&E; Part Number 984862765; Fully compatible with F8627, can be directly replaced
Installation and Maintenance
Insert and lock the slot to ensure reliable connection of the backplane contacts
Connect Ethernet / HSR / Debug interfaces according to specifications, and ground the cabinet reliably
Check the status of indicator lights during daily inspections, regularly tighten terminals and clean dust
Direct replacement of the same model is allowed, no need to reconfigure programs and addresses