F8620/11
May 14, 2026

F8620/11

Basic Information Model: F8620/11 Brand: HIMA Product Type: Safety CPU Controller Module Applicable System: H51q Series Safety Instrumentation System (SIS) Safety Level: IEC 61508 SIL3, TÜV Certified Installation Method: Rack Slot Installation Protection Grade: IP20 Weight: Approximately 0.16kg

Description

黑马7.jpg

Basic Information

Model: F8620/11

Brand: HIMA

Product Type: Safety CPU Controller Module

Applicable System: H51q Series Safety Instrumentation System (SIS)

Safety Level: IEC 61508 SIL3, TÜV Certified

Installation Method: Rack Slot Installation

Protection Grade: IP20

Weight: Approximately 0.16kg

Electrical parameters

Power supply voltage: 5VDC, 24VDC dual power supply, 5V working current: 120mA, 24V working current: 200mA Electrical insulation: Input to ground, communication interface to ground withstand voltage 500V AC/1 minute Built-in protection: Overvoltage, undervoltage, reverse connection, over-temperature, short circuit protection

Hardware performance

Architecture: Triple module redundancy TMR program storage: 1MB Flash data storage: 1MB SRAM Logic processing cycle: ≤20ms SOE event recording: Supports 5000 event storage, timestamp resolution 1ms

Communication interface

Ethernet: 1 path RJ45 Ethernet interface Serial port: 2 paths RS-485 interface System bus: HIMA dedicated redundant safety bus, connects each I/O module Supported protocols: TCP/IP, Modbus RTU, Profibus DP

Environmental parameters

Operating temperature: -25℃ ~ +85℃ Storage temperature: -40℃ ~ +85℃ Relative humidity: 5%~95%, no condensation Vibration and shock performance: Complies with industrial IEC 60068 standard Main function


Using the TMR triple-redundancy architecture, it performs safety logical operations such as ESD, BMS, F&G, etc.

The entire machine has full self-diagnosis, and it can monitor the CPU, memory, bus, communication, and hardware status in real time. Faults will trigger automatic alarm and record.

It supports dual serial ports and redundant communication via the safety bus. In case of link abnormality, it will automatically switch without interrupting the system operation.

It supports hot plugging of modules, allowing for online replacement. After replacement, the program and data will be automatically synchronized.

It has the SOE (Sequence of Events) event sequence recording function, facilitating event traceability and fault analysis. 

Panel Indicator Light Explanation

PWR Green: Normal power supply is constantly on. It goes off when there is an input power anomaly. RUN Green: Normal operation is flashing. It remains on or off when there is an initialization anomaly or failure. ALM Red: Hardware or system failure is constantly on. ETH Yellow: Ethernet connection or data transmission is flashing. COM Yellow: System bus and serial port communication has data flashing.

Installation and Maintenance

Align and push into the rack slot, tighten the panel fixing screws to ensure reliable contact of the backplane. Connect power, Ethernet, serial port, and system bus according to specifications. Ground the cabinet reliably. Daily inspection checks the status of the indicator lights. No alarms and normal communication are sufficient. Regularly check the tightness of terminals, no overheating or oxidation, and clean the dust on the module surface. Module failures can be directly replaced with the same model without modifying the wiring and program.