F7130A
May 14, 2026

F7130A

Basic Information Model: F7130A Brand: HIMA Product category: Safety Isolation DC/DC Power Module Application system: H41q/HIQuad Safety Instrumented System (SIS) Safety certification: IEC 61508 SIL3, TÜV, ATEX Part number: 984713060 Installation method: DIN rail installation Protection level: IP20 Weight: Approximately 1.0 kg

Description

Basic Information

Model: F7130A

Brand: HIMA

Product category: Safety Isolation DC/DC Power Module

Application system: H41q/HIQuad Safety Instrumented System (SIS)

Safety certification: IEC 61508 SIL3, TÜV, ATEX

Part number: 984713060

Installation method: DIN rail installation

Protection level: IP20

Weight: Approximately 1.0 kg

Electrical parameters

Input voltage: 24VDC, allowable fluctuation range -15% to +20%

Input ripple: <15% (rpp)

Recommended input fuse: 5A gL (slow melting type)

Output voltage (CPU/I/O): 5VDC (±0.25V)

Output current (CPU/I/O): Maximum 10A

Output voltage (HIBUS): 5VDC (±0.25V)

Output current (HIBUS): Maximum 1A

Electrical isolation: withstand voltage between input and output is 500V AC

Protection features: overvoltage protection, current limiting protection, short circuit protection, overheat protection

Conversion efficiency: ≥70%

Operating mode: supports dual-module redundant parallel connection Environmental parameters

Operating temperature: -20℃ ~ +60℃

Storage temperature: -40℃ ~ +85℃

Relative humidity: 10% ~ 90%, no condensation

Anti-vibration and shock resistance: Compliant with industrial IEC standards

Core functions

Convert 24VDC to isolated 5VDC, providing power for the CPU, I/O backplane and HIBUS interface of the H41q/HIQuad system

Electrical isolation of input and output, blocking interference

Integrated overvoltage, undervoltage, overcurrent, short circuit and overheating protection, self-protection in case of faults

Independent power supply circuit design, separate power supply for CPU/I/O and HIBUS interface

Panel LED indicators, showing input voltage (L+) and output status

Support for hot swapping, allowing module replacement online

Caution for use

Reserve space for heat dissipation, away from strong interference equipment such as frequency converters and contactors

24V input uses an independent regulated power supply, not connected to high-power loads in the same circuit

The cabinet is reliably grounded, with a grounding resistance of ≤ 4Ω, single-ended grounding of the shielding wire

Ensure consistent output voltage of the two modules during redundant parallel operation to avoid internal circulation

Regularly check terminal fastening, no oxidation, and no condensation

Faults can be directly replaced with the same model without modifying wiring and programs