F7102
May 14, 2026

F7102

F7102 (Material Number 984710201) is the enhanced version of HIMA HIMax series high-end SIL3 safety CPU. It is an upgraded version of F7101, featuring TMR triple redundancy, enhanced computing power, memory and communication capabilities, and fully compatible pins that can be directly interchanged. I. Basic Information Model: F7102 (Material Number: 984710201) Brand/Series: HIMA (Germany, Hima) / HIMax Type: Safety CPU Controller (SIS/ESD core) Safety Level: SIL3, AK6, Cat.4/PL e (TÜV Certified) Architecture: TMR Triple Module Redundancy (Three CPUs Synchronous Voting)

Description

II. Core Parameters (Compared with F7101) Table

Parameters: F7102 (High Configuration) F7101 (Standard)

Processor: Dual-core ARM Cortex-A53, 1.2GHz Dual-core ARM Cortex-A53, 1.2GHz

Program Flash: 4MB (vs 1MB) 1MB

Data SRAM: 4MB (vs 1MB) 1MB

Ethernet: Dual-port 10/100Mbps (RJ45×2) Single-port 10/100Mbps (RJ45×1)

Serial Port: RS-485/RS-232 ×1 RS-485/RS-232 ×1

System Bus: HIMax redundant high-speed bus (HSR) HSR bus

Diagnosis: Full hardware self-diagnosis, fault-safe shutdown Same as left

Power Supply: 5V DC ≈ 200mA; 24V DC ≈ 250mA 5V ≈ 150mA; 24V≈200mA

Power consumption: < 6W, < 5W

Temperature: -20℃ ~ +60℃, -20℃ ~ +60℃

Size/Weight: 4TE (25×203×127mm) / approximately 0.5kg (same as above)

Installation: DIN rail, hot-swappable - same as above

III. Key Upgrade Points (F7102 vs F7101)

Memory ×4: 4MB Flash/4MB SRAM, supports larger program and data volume, complex security logic (such as BMS/F&G).

Dual Ethernet ports: supports network redundancy (such as DCS dual network communication), improves communication reliability.

Enhanced diagnostics: extended communication links / clock synchronization / power redundancy diagnosis, more accurate fault location.

Higher stability: optimized firmware and anti-interference design, suitable for high-load / long-cycle operation scenarios.

IV. Model Interchange and Application

Interchangeability: F7102 and F7101 have fully compatible pins / software, can be directly replaced (ELOP II configuration has no difference).

Typical applications: petrochemical ESD, BMS burner management, F&G fire and gas system, turbine control (TMC) and other medium-large SIS projects.

黑马14.jpg