F67062
Description
**F67062 (Material Number 984670621)** is an upgraded replacement version of HIMA F6706: dual-channel SIL3 safety analog output (4-20mA / 0-10V options available), TMR redundancy, and direct interchangeability.
I. Core Parameters (984670621)
Model: F67062 (Material Number: 984670621)
Function: 2 channels of AO, 4-20mA / 0-10V selectable via software (each channel independently)
Safety Level: SIL3, AK1~AK6, Cat.4/PL e (TÜV Certification)
Architecture: Triple Modular Redundancy (TMR), Integrated Safety Shutdown
Resolution: 12 bits (4096 steps)
Load Capacity:
Current (4-20mA): ≤ 500Ω
Voltage (0-10V): ≥ 10kΩ
Accuracy:
Basic Error: ≤ ±0.1% FS @ 25℃
Operating Error: ≤ ±0.4% FS (0 - +60℃)
Isolation Voltage: 250V AC (Channel to Analog Ground)
Power Supply: 5V DC ≈ 150mA; 24V DC≈200mA
Operating temperature: -20℃ ~ +60℃
Dimensions/Weight: 4TE (25×203×127mm) / Approximately 0.5kg
Installation: DIN rail, supports hot swapping
Diagnosis: Short circuit / Open circuit / Over-range detection, automatic full test during operation
II. Relationship with the standard version F6706 (984670601)
F67062 (984670621): Hardware/firmware upgrade, enhanced diagnostics, stability and anti-interference, batch update, fully interchangeable
F6706 (984670601): Standard version, function is the same, gradually replaced by F67062
III. Main matters (installation / wiring / maintenance)
1. Installation points
Environment: Dust-free, dry, free from corrosion, anti-condensation
Heat dissipation: Maintain a spacing of ≥ 50mm above and below, away from heat sources and strong electricity
Grounding: Independent protection ground of the cabinet ≤ 4Ω, system ground and protection ground separated
Hot swapping: Before online replacement, need to disable the module in the software
2. Wiring specifications (28-pin terminals)
Signal cables: Shielded twisted pair, single-ended grounding (module side)
Cabling: Separate from strong electricity by ≥ 10cm, avoid parallel long-distance wiring
Maximum cable length: 1000m (load resistance needs to be verified)
3. Configuration and calibration
Software configuration: ELOP II sets output type (mA/V), range and fault safety value
Calibration cycle: Recommended once a year; re-calibrate if error exceeds ±0.2% FS
Safety shutdown: Automatically cut off output when a fault occurs, enter safe state