F6706
Description
F6706 is a dual-channel SIL3 safety analog output module from the German HIMA company. It can output 4-20mA or 0-10V signals and is used in safety instrument systems (SIS), with TÜV AK6/SIL3 certification.
1. Core Parameters
Model: F6706 (Part Number: 984670601)
Channels: 2 independent isolated analog outputs
Output signals: 4-20mA (current), 0-10V (voltage), each channel can be selected by software
Resolution: 12 bits (4096 steps)
Accuracy: Typical ±0.1% FS at 25℃; Working error ≤ ±0.4% FS (0 - +60℃)
Load capacity:
Current (4-20mA): ≤ 500Ω
Voltage (0-10V): ≥ 10kΩ
Isolation withstand voltage: 250V AC (channel to analog ground)
Safety level: SIL3, AK1 - AK6, Cat.4/PL e (TÜV)
Response time: Typical 250ms (including filtering and conversion)
Power supply: 5V DC ≈ 150mA; 24V DC≈200mA
Operating temperature: -20℃ ~ +60℃; Storage: -40℃ ~ +85℃
Dimensions/Weight: 4TE (25×203×127mm) / Approximately 0.5kg
Installation: DIN rail, supports hot swapping
Diagnosis: Short circuit / Open circuit / Over-range detection, automatic operation test is available
II. Differences from F6705/F670532
F6706: Dual output of current/voltage is optional (4-20mA / 0-10V), with stronger load capacity (500Ω/10kΩ)
F6705/F670532: Only current output (0/4-20mA), without voltage output
Interchangeability: The pins of the three are compatible and can be directly interchanged, but F6706 has more functions
III. Main Matters (Installation / Wiring / Maintenance)
1. Installation Tips
Environment: Dust-free, dry, without corrosion, anti-condensation
Heat dissipation: Leave a distance of ≥50mm between top and bottom, away from heat sources and strong electricity
Grounding: The independent protection ground of the cabinet ≤4Ω, the system ground is separated from the protection ground
Hot swapping: Before online replacement, the module needs to be disabled in the software
2. Wiring Specifications (28-pin terminals)
Signal cables: Shielded twisted pair, single-ended grounding (module side)
Cabling: Separate the 220V/380V strong current from the wiring ≥10cm, avoid long parallel runs
Maximum cable length: 1000m (load resistance needs to be verified)
Output mode: Source/sink mode software configuration, voltage/current mode hardware jumpers + software settings
3. Configuration and Calibration
Software configuration: ELOP II sets the output type (mA/V), range and fault safety value
Calibration cycle: It is recommended to do once a year; if the error exceeds ±0.2% FS, re-calibration is required
Safety shutdown: Automatically cuts off the output when a fault occurs, enters a safe state
4. Maintenance and Fault Troubleshooting
Status indication: Green LED = normal, red = fault; regularly check the diagnostic log
Common faults:
Incorrect output: Check the wiring, shielding, grounding and load resistance
No output from channel: Check for short circuits / open circuits, replace the channel for testing, if abnormal, replace the module