F622138
Description
F622138 (Material Number 984622138) is an upgraded replacement version of HIMA F6221: 8-channel SIL3 analog input (4–20mA/0–10V), TMR triple redundancy, directly interchangeable.
1. Core Parameters (984622138)
Model: F622138 (984622138)
Function: 8-channel AI, software selectable from 4–20mA/0–20mA/0–5V/0–10V
Safety Level: SIL3, AK6, Cat.4/PL e (TÜV)
Architecture: TMR triple redundancy (hardware voting)
Resolution: 16 bits
Input Impedance: Current ≈ 50Ω; Voltage ≈ 100kΩ
Isolation: Channel - Backplane 200V AC; Channel-to-channel isolation
Accuracy: ±0.1% FS at 25℃; ±0.3% FS at 0–+60℃
Refresh / Response: 50ms; Safety Response < 450ms
Filtering: Hardware low-pass, τ ≈ 10ms
Power Supply: 5V DC ≈ 80mA; 24V DC≈50mA
Temperature: -20℃ ~ +60℃
Dimensions/Weight: 4TE (25×203×127mm) / Approximately 0.5kg
Installation: DIN rail, supports hot swapping
Diagnosis: Open circuit / Short circuit / Overrange / Drift detection
II. Relationship with the Standard Model F6221 (984622102)
F622138 (984622138): Hardware/Firmware upgrade, enhanced performance/diagnosis, batch update, fully interchangeable
F6221 (984622102): Standard model, identical functions
III. Differences from Similar Models F622138 vs F622038
F622138: Analog quantity (4–20mA/0–10V), connected to pressure / level / flow
F622038: Thermocouple (J/K/T...), with cold junction compensation, specifically for temperature measurement F622138 vs F6217
F6217: 12-bit, basic diagnosis
F622138: 16-bit, high precision, strong diagnosis, interchangeable directly
IV. Main Matters (Installation / Wiring / Maintenance)
1. Installation
Environment: Dust-free, dry, free from corrosion, anti-condensation
Heat dissipation: ≥ 50mm above and below, away from heat sources
Grounding: Cabinet independent ground ≤ 4Ω
Hot swapping: Online replacement after disabling software
2. Wiring (28-pin)
Signal: Shielded twisted pair, single-ended grounding (module side)
Cabling: Separate slot from high voltage ≥ 10cm, avoid long parallel runs
Power supply: 24V DC ±10%, reliable connection to GND
3. Configuration and Calibration
Software: ELOP II selects signal type / range / filtering, takes effect after download
Calibration: Once a year; if error > ±0.2% FS, re-calibrate
4. Maintenance and Faults
Status: Green LED = normal, Red = fault; regularly check diagnostic logs
Troubleshooting: Faulty → Wiring / Shielding / Grounding; Channel failure → Replace channel for testing, if abnormal then replace module

Get a Quote