F333038
Description
I. Basic Information
Model: F333038 (F3330 Explosion-proof / High Protection Version)
Brand: HIMA (Germany)
Series: HIMatrix F3 / HIMax
Type: 8-channel SIL3 safety digital output module (DO)
Safety Level: SIL3 (IEC 61508), TÜV AK6, Cat.4/PL e, ATEX Ex ia/ib
Software: SILworX
Applications: ESD/BMS/F&G/SIS, drives explosion-proof solenoid valves, relays, indicator lights
II. Hardware Parameters
Power Supply: 24VDC (L+), 5VDC (backplane)
Power Consumption: 5V @ 110mA; 24V @ 180mA (excluding load)
Channels: 8 DO
Output: 24VDC, per channel 500mA (12W); indicator ≤ 4W
Load: Resistive / Inductive (≤ 12W)
Isolation: Channel-to-channel / Ground safety isolation, explosion-proof isolation
Operating Temperature: -25℃~+70℃ (explosion-proof area -20℃~+50℃)
Size: 4TE (25mm×203mm×127mm)
Weight: Approximately 0.8kg
Hot Swap: Supported
III. Interfaces and Protection
Terminal: 8×DO+, common terminal L-, explosion-proof shielding ground (screw terminal)
Indicator: Per channel LED (operation / fault / explosion-proof status)
Protection: Short circuit / overcurrent / overvoltage / reverse polarity, explosion-proof limiting
Communication: Backplane bus (connected to F3311/F3313/F3318 CPU)
IV. Performance and Safety
Response Time: ≤ 200μs (test signal)
Self-Diagnosis: Channel level (short circuit / open circuit / overload / undervoltage / explosion-proof abnormality)
Fault Behavior: Single channel fault does not affect other channels, system alarm
Safety Mechanism: Output circuit test, safety isolation, fault-safe shutdown
V. Usage Tips
Installation: F3 rack, leave 20mm space for heat dissipation; explosion-proof area complies with ATEX.
Power Supply: 24VDC regulated, FG and explosion-proof shielding ground separated.
Connection: DO + connected to load +, L - connected to load -; for inductive loads, connect a diode (1N4007) in parallel.
Configuration: SILworX adds F3330, define channels, fault response, explosion-proof parameters.
Maintenance: Check terminals / LEDs; locate faults by software; support hot swap.
Compatibility: Compatible with F3311/F3313/F3318 CPU and F32xx DI; configuration needs to be updated when replacing.

Get a Quote