F3221
Description
I. Basic Information
Model: F3221
Series: HIMA F3 (19" rack-mounted safety system, non-closed type F30/F35)
Type: 16-channel DI safety input module (used with F3112/F3114 CPU)
Safety Level: SIL3 (IEC 61508), TÜV Certification; Cat.4/PL e
Programming software: ELOP II (old version)
II. Electrical Specifications
Channels: 16 digital inputs (DI).
Input signals: 24VDC, source type / sink type compatible; 8mA signal or mechanical contacts.
Isolation: Safety isolation of 2kVrms, non-isolated between channels.
Response time: Typical 10ms.
Power supply: 5VDC (backplane) or 24VDC (external); 70mA at 5V, 130mA at 24V.
Diagnosis: Short circuit / open circuit detection, LED status indication.
Environment: 0℃ to +60℃, IP20.
Size/Weight: 19" rack, 4TE width; approximately 0.1kg.
III. Core Features
Safety architecture: Dual-channel redundant input, fail-safe design.
Independent channels: Input channels do not affect each other, single-channel failure does not affect other channels.
Backplane bus: Special safety bus of F3 series, communicates with F3112/F3114 and others.
Installation: 19" rack F3 cabinet, hot-swappable support.
IV. Differences from Modules in the Same Series
F3113A: 16-channel DI module, F3 series, discontinued.
F3221: 16-channel DI module, F3 series, higher isolation voltage (2kV), faster response (10ms).
F3211: 16-channel DO module, F3 series, relay output.
V. Alternative Suggestions
Direct replacement: F3113A (same specification 16DI, good compatibility).
Module replacement: F3DIO8/801 (8DI + 8DO, SIL3, DIN rail).
System upgrade: HIMatrix F35 or HIMax (SILworX, modern communication, full series I/O).


Get a Quote