PR6423/010-130-CON021
Description
I. Model Interpretation PR6423/010-130
PR6423: Φ8mm Eddy Current Sensor
010: Cable length 10m, armored type
130: Special calibration code, standard sensitivity version
CON021: EPRO companion dedicated preamplifier, perfectly matched for use with this probe set
II. Core Parameters of the Sensor
Probe Specifications: Diameter 8mm, M10×1 threaded installation
Cable: 10 meters, double-layer shielded armored cable, anti-interference and anti-tension
Standard Linear Measurement Range: 0 - 1.5mm
Rated Sensitivity: 12V/mm
Standard Installation Gap: 2.5mm
Matching CON021 Mid-point Voltage: -12V
Frequency Response: 0 - 12kHz
DC Resistance of the Coil: 4 - 6Ω
Insulation Resistance: > 100MΩ
Operating Temperature: Probe -35°C to +150°C
Protection Level: IP67
Compatible Target Materials: 42CrMo4 ferromagnetic alloy steel
III. Parameters of the CON021 Preamplifier
Power Supply for Operation: -24VDC, allowable range -18 to -30VDC
Output Linear Voltage Range: -4V to -20V
Power Consumption: ≤ 2W
Frequency Response: 0 - 10kHz
Built-in Protection: Reverse connection, short circuit, open circuit protection
Installation Method: Fixed on the panel inside the cabinet, protection level IP20
IV. Wiring and Connection
CON021 Terminal Definitions
Terminal 1: -24V
Terminal 2: 0V Ground
Terminal 3: Signal Output (connected to MMS6110/MMS6312 etc. TSI modules)
Terminal 4: Signal Common Ground
Sensor and Preamplifier
PR6423 comes with LEMO aviation connector, directly inserted into the CON021 interface and tightened for locking.
Shielding Grounding Specification
Single-point Grounding: Ground only at the preamplifier side of the cabinet, the probe end shield is floating, and grounding at both ends is prohibited.
V. Installation and Commissioning Standards
The probe should be vertically aligned with the measured axis surface, avoiding the axis edge.
Pre-set Installation Gap: 2.5mm
Power On Adjustment of the Probe Position, make CON021 output stable at -12V and then lock for fixation
Sensor Cable Should Be Away from Power Lines, Frequency Converters, and Avoid Parallel Wiring to Avoid Interference
VI. Voltage Status Judgment
Gap is too small: Output is close to -4V
Standard Working Point: 2.5mm ➜ -12V
Gap is too large: Output is close to -20V
No Voltage: Probe broken wire, LEMO connector loose, power polarity reversed
VII. Application Scenarios
Used for steam turbines, compressors, fans, gas turbines
Measurement: Axial vibration, axial displacement, eccentricity, phase difference
Compatible Systems: MMS6000, AMS6500 full series TSI systems