Product Specification – X20BR9300
Description

Product Specification – X20BR9300
1. General Information
Manufacturer: B&R Industrial Automation
Part Number: X20BR9300
Product Type: X2X Link Bus Receiver Module (with integrated power supply)
Product Series: X20 Distributed I/O System
B&R ID Code: 0x1BC1
Certifications: CE, UKCA, cULus, EAC, KC, ATEX Zone 2 (II 3G Ex nA nC IIA T5 Gc)
Product Status: Active mass production
Protection Class: IP20
2. Product Overview
3. Technical Specifications
3.1 Electrical Parameters
X2X Link Power Supply
Input Voltage: 24 VDC (-15% / +20%)
Input Current: Max. 0.7 A
Nominal Output Power: 7 WB& R Industrial Automation
Reverse Polarity Protection: Yes (integrated, non-replaceable fuse)
Overload Protection: Short-circuit proof, temporary overload protectionB& R Industrial Automation
Redundancy: Supports parallel/redundant operation with multiple supply modulesB& R Industrial Automation
Power Consumption: 1.62 WB& R Industrial Automation
I/O Power Supply
Input Voltage: 24 VDC (-15% / +20%)B& R Industrial Automation
Output Voltage: 24 VDCB& R Industrial Automation
Max. Contact Load: 10 AB& R Industrial Automation
Fusing: Requires external max. 10 A slow-blow line fuseB& R Industrial Automation
Reverse Polarity Protection: NoB& R Industrial Automation
Power Consumption: 0.6 WB& R Industrial Automation
Isolation & Communication
Isolation: Full galvanic isolation between field power, X2X Link, and logicB& R Industrial Automation
Backplane Bus: X2X Link high-speed internal communication busB& R Industrial Automation
3.2 Mechanical Parameters
Module Width: 12.5 mmB& R Industrial Automation
Weight: Approx. 0.1 kg
Mounting: Standard DIN rail
Required Accessories:
1 x Terminal Block: X20TB12 (sold separately)B& R Industrial Automation
1 x Bus Base Module: X20BM01 (sold separately)B& R Industrial Automation
Hot Swap: Not applicable (station head module)
3.3 Environmental Conditions
Operating Temperature:
Horizontal: -25 °C to +60 °CB& R Industrial Automation
Vertical: -25 °C to +50 °CB& R Industrial Automation
Storage / Transport Temperature: -40 °C to +85 °CB& R Industrial Automation
Relative Humidity: 5% ~ 95% RH, non-condensingB& R Industrial Automation
Vibration/Shock: Complies with IEC 60068
Altitude: Up to 2000 m (derating applies above 2000 m)
3.4 Diagnostics & Status
Status LEDs: X2X Bus Status, Overload, Operating State, Module ErrorB& R Industrial Automation
Diagnostic Feedback: Module status, bus status, and overload conditions via LED and softwareB& R Industrial Automation
4. Key Features
Station Starter Module: Must be installed in the leftmost slot to initiate an X20 stationB& R Industrial Automation.
Dual Power Feeding: Supplies both the X2X communication bus and the I/O module power.
Full Galvanic Isolation: Protects the controller from field-side voltage transients and noise.
Redundancy Support: Allows parallel connection of multiple units for X2X Link power redundancyB& R Industrial Automation.
Integrated Fuse Protection: Built-in protection for the bus power circuit.
Comprehensive Diagnostics: LED and software-based status monitoring for reliable operation.
ATEX Certification: Safe for use in Zone 2 hazardous locations.
Slim Design: 12.5 mm width for high-density cabinet installation.
5. Typical Applications
Serving as the starting point (leftmost module) for any X20 I/O station.
Connecting remote X20 I/O blocks to a central B&R controller via X2X Link.
Providing galvanic isolation between the field I/O and the control system.
Building distributed I/O systems in process automation, machinery, and factory automation.
Applications requiring safe power distribution in Zone 2 hazardous areas.
Systems demanding high reliability through power supply redundancy.
6. Compatibility
Required Companion Modules: Must be used with X20BM01 bus base moduleB& R Industrial Automation.
I/O Compatibility: Fully compatible with all standard X20 I/O slices (digital, analog, temperature, etc.).
Terminal Blocks: Requires X20TB12 terminal block for power and bus connectionsB& R Industrial Automation.