General Information Manufacturer: B&R Industrial Automation Part Number: X20BC0087 Product Type: Bus Controller (Modbus TCP/UDP Slave Interface) Product Series: X20 Distributed I/O System B&R ID Code: 0x227CB& R Industrial Automation Product Status: Active (In Production) Protection Rating: IP20B& R Industrial Automation Certifications: CE, UKCA, cULus, cCSAus, ATEX (Zone 2, II 3G Ex nA nC IIA T5 Gc)B& R Industrial Automation

Description

贝加莱3.jpg

Product Specification – X20BC0087

1. General Information

  • Manufacturer: B&R Industrial Automation

  • Part Number: X20BC0087

  • Product Type: Bus Controller (Modbus TCP/UDP Slave Interface)

  • Product Series: X20 Distributed I/O System

  • B&R ID Code: 0x227CB& R Industrial Automation

  • Product Status: Active (In Production)

  • Protection Rating: IP20B& R Industrial Automation

  • Certifications: CE, UKCA, cULus, cCSAus, ATEX (Zone 2, II 3G Ex nA nC IIA T5 Gc)B& R Industrial Automation

2. Product Overview

The X20BC0087 is a bus controller module for the B&R X20 I/O system, designed to interface an X20 I/O station as a slave device to a Modbus TCP/UDP network. It serves as a communication gateway, transferring process data and diagnostics between the Modbus master and the local X20 I/O modules via the X2X Link backplane. The module integrates a 2-port Ethernet switch for flexible network topologies.

3. Technical Specifications

3.1 Fieldbus Interface (Modbus TCP/UDP)

  • Protocol: Modbus TCP, Modbus UDP (Slave)B& R Industrial Automation

  • Connectors: 2 x RJ45 (10/100BASE-TX)

  • Transfer Rate: 10/100 Mbit/s (Auto-Negotiation)

  • Duplex Mode: Half / Full duplex

  • Cable Distance: Max. 100 m per segment

  • Switch Features: Auto-MDI/MDIX, integrated 2-port switch

  • Network Configuration: DHCP / BootP capableB& R Industrial Automation

  • I/O Cycle: Configurable (0.5 ms – 4 ms)B& R Industrial Automation

  • Response Time: < 1 – 8 ms (load-dependent)B& R Industrial Automation

3.2 X2X Link Backplane Interface

  • Bus System: X2X Link (internal X20 backplane)

  • Hot-Swappable: Yes

  • I/O Capacity: Supports full range of X20 I/O modules

3.3 Electrical Characteristics

  • Supply Voltage: 24 VDC (from X20 bus base)

  • Power Consumption: 2 WB& R Industrial Automation

  • Isolation: Full galvanic isolation (fieldbus / X2X Link / I/O)B& R Industrial Automation

  • Protection: Reverse polarity, overvoltage, short-circuit

3.4 Mechanical Specifications

  • Dimensions: 37.5 mm (W) × 102 mm (H) × 70 mm (D)B& R Industrial Automation

  • Weight: Approx. 0.05 kg

  • Mounting: Standard DIN rail

  • Module Width: 37.5 mmB& R Industrial Automation

3.5 Environmental Specifications

  • Operating Temperature:

    • Horizontal: -25 °C to +60 °C

    • Vertical: -25 °C to +50 °C

  • Storage / Transport: -40 °C to +85 °CB& R Industrial Automation

  • Humidity: 5–95% RH (non-condensing)B& R Industrial Automation

  • Vibration/Shock: IEC 60068 compliant

3.6 Status Indicators

  • Module Status LED: Green (Run), Red (Error)B& R Industrial Automation

  • Bus Function LED: Yellow (Bus active)B& R Industrial Automation

3.7 Diagnostics

  • Comprehensive module, bus, and I/O diagnosticsB& R Industrial Automation

  • LED status indicationB& R Industrial Automation

  • Software-based diagnostics via Automation StudioB& R Industrial Automation

  • Command sequence validity checkB& R Industrial Automation

4. Key Features

  • Modbus TCP/UDP Slave interface for broad compatibilityB& R Industrial Automation

  • Integrated 2-port Ethernet switch for daisy-chainingB& R Industrial Automation

  • Auto-negotiation & Auto-MDI/MDIX for easy setup

  • Flexible network addressing (DHCP/BootP)B& R Industrial Automation

  • Configurable I/O cycle timesB& R Industrial Automation

  • Full galvanic isolationB& R Industrial Automation

  • ATEX Zone 2 hazardous area approvalB& R Industrial Automation

  • Hot-swappable design

  • Global certifications

5. Typical Applications

  • Connecting X20 I/O to Modbus TCP/UDP systems

  • Third-party PLC integration (Modbus masters)

  • Legacy system modernization

  • Factory automation & process control

  • Hazardous location (Zone 2) installationsB& R Industrial Automation

  • Material handling & packaging machinery

6. System Compatibility

  • Bus Base Module: X20BB80 (required)B& R Industrial Automation

  • Power Supply: X20PS9400, X20PS9402B& R Industrial Automation

  • I/O Modules: All X20 analog, digital, temperature modules

  • Software: B&R Automation Studio

7. Reliability & Support

  • Industrial-grade design for continuous 24/7 operation

  • Maintenance-free passive components

  • Long-term product availability

  • Global technical support & service network

  • Comprehensive documentation & certification files


Get a Quote